9 start requiremt, 10 shut-down requ, Start requiremt – SMA SC 400HE User Manual
Page 100: Shut-down requ
9 Parameters
SMA Solar Technology AG
100
SC4-63HE-BE-BEN103280
Operating Manual
9.9 Start Requiremt
*Only modify these parameters after consultation with SMA Solar Technology AG.
9.10 Shut-down Requ.
*Only modify parameters after consultation with SMA Solar Technology AG.
Name
Description
Value /
range
Explanation
Default
value
Operating
Mode
*
Condition for starting up the
inverter
MPP
Maximum power point
tracking
MPP
VconstSet Target value for constant
voltage operation
VconstSet
Target value for constant
voltage operation
300 V …
700 V
600 V
VpvStart
PV voltage that must be
exceeded for the inverter to
switch into feed-in operation
300 V …
1 000 V
SC 400HE-11
600 V
300 V …
1 000 V
SC 500HE-11
600 V
300 V …
1 000 V
SC 630HE-11
650 V
Tstart
Time span until the inverter
switches from the "Waiting"
operating state to "Startup"
1 s …
600 s
90 s
Twait
Time span until the inverter tries
to start up again after 3 failed
attempts
0 s …
18 000 s
600 s
Name
Description
Value / range
Default
value
PpvStop
*
PV power before the inverter switches into the
"Waiting" operating state after time "TStop".
0 W … 10 000 W
5 000 W
Tstop
Time span until the inverter switches into the
"Startup" operating state if the array power
"Ppv" < "PpvStop"
60 s … 600 s
60 s