7 Troubleshooting

Operating Manual

SC4-63HE-BE-BEN103280

87

7.5 Events

420

Error text:
ADAPSCP Overtemperature

Error type 3

Failure cause:
Heat sink temperature is too high (hardware threshold)
Corrective measures:

• Check the function of the inverter bridge cooling fans.
• Clean soiled air inlet or heat sink.
• Ambient or cooling air temperature too high.
• Contact the SMA Serviceline if the error occurs frequently.

421

Error text:
ADAPSCP Overvoltage DC Voltage link

Error type 2

Failure cause:
DC voltage is too high on the generator side (hardware threshold).
Corrective measures:

• Immediately disconnect the PV array from the Sunny Central! Danger of damage to

the Sunny Central!

• Check the DC voltage.
• Check module wiring and plant design.

Information:

• If the failure poses a danger to the PV plant or the Sunny Central, the Sunny Central

switches into the "Waiting" operating state for 30 minutes.

Event

Explanation

> LVRT

Low Voltage Ride Through (LVRT) is active

> Net-Parameter

Grid parameters are set incorrectly

> NSM

Power limitation via grid management activated

< NSM

Power limitation via grid management deactivated

> FRQ-Derating

Frequency-dependent output limitation activated

< FRQ-Derating

Frequency-dependent output limitation deactivated