11 grid monitor, 12 other, Grid monitor – SMA SC 400HE User Manual
Page 101: Other
SMA Solar Technology AG
9 Parameters
Operating Manual
SC4-63HE-BE-BEN103280
101
9.11 Grid Monitor
*Only modify parameters after consultation with SMA Solar Technology AG.
9.12 Other
*Only modify parameters after consultation with SMA Solar Technology AG.
Name
Description
Value / range Explanation
Default
value
PpvMinCheck
*
Procedure for shut-
down requirements
On
Inverter implements shut-
down requirement limits.
On
Off
The inverter continues to
operate if the shutdown
conditions have not yet
been met.
Grid disconnection Activation of grid
disconnection
On
Grid disconnection
activated
On
Off
Grid disconnection
deactivated
Name
Description
Value / range
Default
value
E-Total Offset
Offset for the device's internal energy
counter. It is advisable to change this
parameter after replacing the
Sunny Central Control.
0 kWh …
429 496 000 kWh
0 kWh
TMax. cabinet
*
Maximum temperature of the inverter
cabinet. If "TMax. cabinet" is exceeded,
the warning "cabinet Temp." will be
generated.
30°C … 70°C
60°C
TMin. cabinet
*
Minimum temperature of the inverter
cabinet. If the value is below
"TMin. cabinet", the warning "cabinet
Temp." will be generated.
‒30°C ... 10°C
‒20°C
TmpDrtStopMod
Settings for the temperature derating This
parameter is used to activate or deactivate
the temperature derating.
On
On
Off
SC_RemoteGFDI
*
Setting for Remote GFDI
This parameter is used to activate or
deactivate Remote GFDI.
On
Off
Off