SMA Solar Technology AG

9 Parameters

Operating Manual

SC4-63HE-BE-BEN103280

101

9.11 Grid Monitor

*Only modify parameters after consultation with SMA Solar Technology AG.

9.12 Other

*Only modify parameters after consultation with SMA Solar Technology AG.

Name

Description

Value / range Explanation

Default
value

PpvMinCheck

*

Procedure for shut-
down requirements

On

Inverter implements shut-
down requirement limits.

On

Off

The inverter continues to
operate if the shutdown
conditions have not yet
been met.

Grid disconnection Activation of grid

disconnection

On

Grid disconnection
activated

On

Off

Grid disconnection
deactivated

Name

Description

Value / range

Default
value

E-Total Offset

Offset for the device's internal energy
counter. It is advisable to change this
parameter after replacing the
Sunny Central Control.

0 kWh …

429 496 000 kWh

0 kWh

TMax. cabinet

*

Maximum temperature of the inverter
cabinet. If "TMax. cabinet" is exceeded,
the warning "cabinet Temp." will be
generated.

30°C … 70°C

60°C

TMin. cabinet

*

Minimum temperature of the inverter
cabinet. If the value is below
"TMin. cabinet", the warning "cabinet
Temp." will be generated.

‒30°C ... 10°C

‒20°C

TmpDrtStopMod

Settings for the temperature derating This
parameter is used to activate or deactivate
the temperature derating.

On

On

Off

SC_RemoteGFDI

*

Setting for Remote GFDI
This parameter is used to activate or
deactivate Remote GFDI.

On

Off

Off