Series 3
Operations Manual
79
Parameter
Mnemonic
Parameter Name
Modbus Address
Decimal
12 – Auto/Manual
13 – Remote fail
14 – Power fail
15 – FEATURE UNAVAILABLE
1.SRC.B
IO Channel 1 Source B
As IO Channel 1 Source A (Modbus address 12678)
12679
1.SRC.C
IO Channel 1 Source C
As IO Channel 1 Source A (Modbus address 12678)
12680
1.SRC.D
IO Channel 1 Source D
As IO Channel 1 Source A (Modbus address 12678)
12681
1.SENS
Configures the polarity of the input or output channel (0 = Normal, 1 = Inverted)
12682
1.PLS
IO1 Time proportioning Output minimum pulse time
12706
2.ID
Output 2 Type
0 – None
1 – Relay
2 – Logic Output
3 – DC OP
4 – Triac (SSR)
12736
2.FUNC
Output 2 Channel function
0 – None (or Telemetry Output)
1 – Digital Output
2 – Heat or UP if valve position
3 – Cool or DOWN if valve position
10 – DC Output no function
11 – DC Output Heat
12 – DC Output Cool
13 – DC Output WSP retransmission
14 – DC Output PV retransmission
15 – DC Output OP retransmission
12739
2.RNG
IO Channel 2 DC Output Range
0 – 0-20mA
1 – 4-20mA
12740
2.SRC.A
Output 2 source A
As IO Channel 1 Source A (Modbus address 12678)
12742
2.SRC.B
Output 2 source B
As IO Channel 1 Source A (Modbus address 12678)
12743
2.SRC.C
Output 2 source C
As IO Channel 1 Source A (Modbus address 12678)
12744
2.SRC.D
Output 2 source D
As IO Channel 1 Source A (Modbus address 12678)
12745
2.SENS
Output 2 Polarity (0 = Normal, 1 = Inverted)
12746
2.PLS
Output 2 Time proportioning Output minimum pulse time
12770
3.ID
Output 3 Type
0 – None
1 – Relay
2 -
3 – DC OP
12800
3.FUNC
Output 3 Channel function
0 – None (or Telemetry Output)
1 – Digital Output
2 – Heat or UP if valve position
3 – Cool or DOWN if valve position
10 – DC Output no function
11 – DC Output Heat
12 – DC Output Cool
13 – DC Output WSP retransmission
14 – DC Output PV retransmission
15 – DC Output OP retransmission
12803
3.RNG
IO Channel 3 DC Output Range
0 – 0-20mA
1 – 4-20mA
12804
3.SRC.A
Output 3 source A
As IO Channel 1 Source A (Modbus address 12678)
12806
3.SRC.B
Output 3 source B
As IO Channel 1 Source A (Modbus address 12678)
12807