3 alarm parameters, Alarm parameters – Super Systems 3 Series User Manual
Page 66

Operations Manual
Series 3
66
12.3
Alarm Parameters
Four alarms are available. Parameters do not appear if the Alarm Type = None. The following table shows the parameters to set
up and configure alarms.
ALARM LIST
‘ALARM’
Name
Scrolling Display
Parameter Description
Value
Default
Access
Level
A1.TYP
ALARM 1 TYPE
Selects the type of alarm
none
Alarm not configured
Conf
Hi
Full Scale High
Lo
Full Scale Low
d.Hi
Deviation High
d.Lo
Deviation Low
bnd
Deviation band
rrc
Rising rate of change,
set in 1-9999 eng
units/min
Frc
Falling rate of change
set in 1-9999 eng
units/min
A 1 . - - -
ALARM 1 SETPOINT
Alarm 1 threshold value.
The last three characters show the
type of alarm configured from the
above list
Instrument range
0
L3
A 1 . s t s
ALARM 1 OUTPUT
Indicates the status of the alarm
OFF
Alarm off
Read only
On
Alarm on
A1.HYS
ALARM 1
HYSTERESIS
See description at the beginning of
this section
0 to 9999
Conf
A1.LAT
ALARM 1
LATCHING TYPE
See description at the beginning of
this section
none
Non-latching
Conf
Auto
Latching with
automatic resetting
Man
Latching with manual
resetting
Evt
Event (no alarm
flashing beacon but
messages can be
displayed)
A1.BLK
ALARM 1
BLOCKING
See description at the beginning of
this section
No
No blocking
No
Conf
yes
Blocking
The above parameters are repeated for Alarm 2, A2; Alarm 3, A3; Alarm 4, A4