Super Systems 3 Series User Manual
Page 76

Operations Manual
Series 3
76
Parameter
Mnemonic
Parameter Name
Modbus Address
Decimal
PNT.LO
Adjust Low Point
563
CT.RNG
CT Range
572
Sb.tyP
Sensor Break Type
0 – No Sensor Break
1 – Non-Latching Sensor Break
2 – Latching Sensor Break
578
Id
Customer ID – May be set to any value between 0-9999 for identification of instruments in applications. Not used by the
instrument itself.
629
PHASE
Calibration Phase
0 – None
1 – 0 mv
2 – 50 mv
3 – 150 Ohm
4 – 400 Ohm
5 – CJC
6 – CT 0 mA
7 – CT 70 mA
8 – Factory Defaults
9 – Output 1 mA low cal
10 – Output 1 mA high cal
11 – Output 2 mA low cal
12 – Output 2 mA high cal
13 – Output 3 ma low cal
14 – Output 3 ma high cal
15 – Remote setpoint input low volts
16 - Remote setpoint input high volts
17 - Remote setpoint input low current
18 - Remote setpoint input high current
768
GO
Calibration Start
0 – No
1 – Yes (start cal)
2 – Cal Busy
3 – Cal Pass
4 – Cal Fail
Note values 2-4 cannot be written but are status returns only
769
-
Analogue Output Calibration Value
775
K.LOC
Allows instrument to be locked via a key/digital input
0 - unlocked,
1 – all keys locked
2 – Edit keys (raise and lower) disabled
3 – Mode key disabled
4 – Manual mode disabled
5 – Enter standby mode when Mode combination pressed
1104
Dwel.1
FEATURE NOT AVAILABLE
1280
TSP.1
FEATURE NOT AVAILABLE 1
1281
RMP.1
FEATURE NOT AVAILABLE
1282
Dwel.2
FEATURE NOT AVAILABLE
1283
TSP.2
FEATURE NOT AVAILABLE
1284
RMP.2
FEATURE NOT AVAILABLE
1285
Dwel.3
FEATURE NOT AVAILABLE
1286
TSP.3
FEATURE NOT AVAILABLE 3
1287
RMP.3
FEATURE NOT AVAILABLE 3
1288
Dwel.4
FEATURE NOT AVAILABLE
1289
TSP.4
FEATURE NOT AVAILABLE 4
1290
RMP.4
FEATURE NOT AVAILABLE
1291
AT.R2G
Auto-tune Configures R2G
0 - YES
1 - No
4176
IN.TYP
Input Sensor Type
0 – J Type Thermocouple
1 – K Type Thermocouple
2 – L Type Thermocouple
3 – R Type Thermocouple
12290