Super Systems 3 Series User Manual
Page 78

Operations Manual
Series 3
78
Parameter
Mnemonic
Parameter Name
Modbus Address
Decimal
1 – Working Setpoint
2 – PV
3 – Output Power
4 – Error
REG.AD
Modbus register address to broadcast retransmission to. For example if you wish to retransmit the working setpoint from one
Series 3 to a group of slaves, and receive the master working setpoint into the slaves’ remote setpoint, set this variable to 26
(the address of the remote setpoint in the slave units).
12552
Ct.Id
Current Transformer
12608
CT.SRC
CT Source
0 – None
1 – IO1
2 – OP2
8 – AA (OP4)
12609
CT.LAT
CT Alarm Latch Type
0 – No latching
1 – Latch – Automatic Reset
2 – Latch – Manual Reset
12610
1.ID
IO channel 1 hardware type
0 – None
1 – Relay
2 – Logic I/O
3 – DC OP
4 – Triac (SSR)
12672
1.D.IN
IO1 Digital input function
Logic input function
40 – None
41 – Acknowledge all alarms
42 – Select SP1/2
43 – Lock All Keys
44 – FEATURE NOT AVAILABLE
45 – FEATURE NOT AVAILABLE
46 – FEATURE NOT AVAILABLE
47 – FEATURE NOT AVAILABLE
48 – Auto/Manual Select
49 – Standby Select
50 – Remote setpoint
51 – Recipe select through IO1
52 – Remote key UP
53 – Remote key DOWN
12673
1.Func
I/O Channel Function
0 – None (or Telemetry Output)
1 – Digital Output
2 – Heat or UP if valve position
3 – Cool or DOWN if valve position
4 – Digital Input
10 – DC Output no function
11 – DC Output Heat
12 – DC Output Cool
13 – DC Output WSP retransmission
14 – DC Output PV retransmission
15 – DC Output OP retransmission
12675
1.RNG
IO Channel 1 DC Output Range
0 – 0-20mA
1 – 4-20mA
12676
1.SRC.A
IO Channel 1 Source A
0 – None
1 – Alarm 1
2 – Alarm 2
3 – Alarm 3
4 – Alarm 4
5 – All Alarms (1-4)
6 – New Alarm
7 – CT Alarm (Load, Leak or Overcurrent)
8 – Loop Break Alarm
9 – Sensor Break Alarm
10 – FEATURE NOT AVAILABLE
11 – FEATURE UNAVAILABLE
12678