Operations Manual
Series 3
22
Mnemonic
Scrolling Display and description
Range
WKG.SP
WORKING SETPOINT is the active setpoint value and appears when the controller is
in Manual mode. It may be derived from SP1 or SP2, or, if the controller is ramping
(see SP.RAT), it is the current ramp value.
SP.HI to SP.LO
WRK.OP
WORKING OUTPUT is the output from the controller expressed as a percentage of
full output. It appears when the controller is in Auto mode.
For a time proportioning output, 50% = relay or logic output on or off for equal
lengths of time.
For On/Off control: OFF = <1%. ON = >1%
Read only value
0 to 100% for heating
0 to –100% for cooling
-100 (max cooling) to 100% (max
heating
T.STAT
FEATURE UNAVAILABLE
Reset
rES
Running
run
Hold
hoLd
End
Timed out
UNITS
DISPLAY UNITS Temperature display units. ‘Percentage’ is provided for linear
inputs
O
C
Degrees C
O
F
Degrees F
O
k
Degrees K
nonE
None
PErc
Percentage
SP.HI
SETPOINT HIGH High setpoint limit applied to SP1 and SP2.
Alterable between range limits
SP.LO
SETPOINT LOW Low setpoint limit applied to SP1 and SP2
By default the remote setpoint is scaled between SP.HI and SP.LO. Two further parameters (REM.HI and REM.LO) are
available in access level 3 to limit the Remote SP range if required.
SP1
SETPOINT 1 allows control setpoint 1 value to be adjusted
Alterable: SP.HI to SP.LO
SP2
SETPOINT 2 allows control setpoint 2 value to be adjusted
Alterable: SP.HI to SP.LO
SP.RAT
SETPOINT RATE LIMIT Rate of change of setpoint value.
OFF to 3000 display units per
minute
The next section applies to the Timer only.
TM.CFG
FEATURE UNAVAILABLE
none
None
Dwel
Dwell
DeLy
Delayed switch on
sfst
Soft start
TM.RES
FEATURE UNAVAILABLE
Hour
min
Hours
Minutes
THRES
FEATURE UNAVAILABLE
OFF or 1 to 3000
END.T
FEATURE UNAVAILABLE
OFF
Control OP goes to zero
Dwel
Control continues at SP1
SP2
Go to SP2
SS.PWR
FEATURE UNAVAILABLE
-100 to 100%
SS.SP
FEATURE UNAVAILABLE
Between SP.HI and SP.LO
DWELL
FEATURE UNAVAILABLE
0:00 to 99.59 hh:mm: or mm:ss
T.REMN
FEATURE UNAVAILABLE
0:00 to 99.59 hh:mm: or mm:ss
The following parameters are available when the timer is configured as a programmer.
SERVO
FEATURE UNAVAILABLE
SP
Setpoint
PV
Process variable
SP.rb
Ramp back to SP
PV.rb
Ramp back to PV
TSP.1
TARGET SETPOINT 1. To set the target value for the first setpoint
RMP.1
FEATURE UNAVAILABLE
OFF, 0:01 to 3000 units per min or
hour as set by TM.RES