INPUT LIST
I N P U T
Name
Scrolling Display
Parameter Description
Value
Default
Access Level
R c . f t
ROC FILTER TIME
This provides a first order filter for
the rate of change filtering function
and can be used to avoid nuisance
alarm triggers due to short duration
noise on the calculated rate of
change,
oFF
to 0.1 to 999.9 minutes
Off means no filtering applied
1.6
L3
R C . P V
PV DERIVATIVE
Provides a measure of the calculated
rate of change of the temperature or
measurement input as used by the
Rate of Change Alarm functions.
Useful when commissioning to
determine the level of filtering
required on the Rate of Change
alarm.
L3
8.1.1
Input Types and Ranges
Input Type
Min Range
Max Range
Units
Min Range
Max Range
Units
J.tc
Thermocouple type J
-210
1200
o
-346
C
2192
o
F
k.tc
Thermocouple type K
-200
1372
o
-328
C
2502
o
F
L.tc
Thermocouple type L
-200
900
o
-328
C
1652
o
F
r.tc
Thermocouple type R
-50
1700
o
-58
C
3092
o
F
b.tc
Thermocouple type B
0
1820
o
32
C
3308
o
F
n.tc
Thermocouple type N
-200
1300
o
-328
C
2372
o
F
t.tc
Thermocouple type T
-200
400
o
-328
C
752
o
F
S.tc
Thermocouple type S
-50
1768
o
-58
C
3215
o
F
Rtd
Pt100 resistance thermometer
-200
850
o
-328
C
1562
o
F
mv
mV or mA linear input
-10.00
80.00
Cms
Value received over digital
communications (modbus address
203).
This value must be updated every 5
seconds or the controller will show
sensor break