Super Systems 3 Series User Manual
Page 75

Series 3
Operations Manual
75
Parameter
Mnemonic
Parameter Name
Modbus Address
Decimal
0 – Linear
1 – Oil
2 – Water
3 – Fan
DEC.P
Decimal Point Position
0 – XXXX.
1 – XXX.X
2 – XX.XX
525
STBY.T
Standby Type
0 – Absolute Alarm Outputs Active – others off
1 – All outputs inactive
530
RAMP
UNITS
0 – Ramp per Minute
1 – Ramp per Hour
2 – Ramp per Second
531
Meter
Ammeter configuration
0 – No ammeter
1 – Heat Output (0-100%)
2 – Cool Output (0-100% cooling)
3 – Working Setpoint (scaled within SP limits)
4 – PV (scaled within range)
5 – Output Power (scaled within Op Low and OP High limits)
6 – Output centered between –100% and 100%
7 – Error (PV-SP) (scaled between +/- 10 degrees)
8 – Instantaneous Amps (scaled 0 to CT Span)
9 – Load Current (scaled 0 to CT Span)
532
uCAL
User Calibration Enable
533
A1.TYP
Alarm 1 Type
0 – Off
1 –Absolute High
2 – Absolute Low
3 – Deviation High
4 – Deviation Low
5 – Deviation Band
536
A2.TYP
Alarm 2 Type
(as Alarm 1 Type)
537
A3.TYP
Alarm 3 Type
(as Alarm 1 Type)
538
A4.TYP
Alarm 4 Type
(as Alarm 1 Type)
539
A1.LAT
Alarm 1 Latching Mode
0 – No latching
1 – Latch - Automatic Reset
2 – Latch – Manual Reset
540
A2.LAT
Alarm 2 Latching Mode
(as Alarm 1 Latching Mode)
541
A3.LAT
Alarm 3 Latching Mode
(as Alarm 1 Latching Mode)
542
A4.LAT
Alarm 4 Latching Mode
(as Alarm 1 Latching Mode)
543
A1.BLK
Alarm Blocking Mode Enable (0 = OFF, 1 = BLOCK)
544
A2.BLK
Alarm Blocking Mode Enable (0 = OFF, 1 = BLOCK)
545
A3.BLK
Alarm Blocking Mode Enable (0 = OFF, 1 = BLOCK)
546
A4.BLK
Alarm Blocking Mode Enable (0 = OFF, 1 = BLOCK)
547
Di.OP
Digital Outputs Status. This is a bitmap:
B0 – Output 1A
B1 – Output 2A
B3 – Output 4/AA
It is possible to write to this status word to use the digital outputs in a telemetry output mode. Only outputs whose function is
set to ‘none’ are affected, and the setting of any bits in the Digital Output Status word will not affect outputs used for heat (for
example) or other functions. Thus it is not necessary to mask in the settings of these bits when writing to this variable.
551
OFS.HI
Adjust High Offset
560
OFS.LO
Adjust Low Offset
561
PNT.HI
Adjust High Point
562