CONTROL LIST
‘CTRL’
Parameter
Name
Parameter Description
(Scrolling Display)
Value
Default
Access
Level
O P . L O
OUTPUT LOW
Adjust to limit the maximum cooling
power applied to the process or to
apply a minimum heating power
+100.0%
0.0 (heat
only)
-100
(cool)
L3
D . B A N D
CHANNEL 2 DEAD BAND
Period when no output is demanded
from either channel 1 or channel 2
Adjust, for example, to increase the
period when no heating or cooling
power is applied
Off
or 0.1 to 100.0% of the cooling proportional
band
OFF
L3
H Y S T . H
HEATING HYSTERESIS
1 to 9999 display units
1
L3 On/off
only
H Y S T . C
COOLING HYSTERESIS
1
S A F E
SAFE OUTPUT POWER
To set the output level in a sensor break
(open circuit) condition
-100.0 to 100.0% limited by OP.HI and OP.LO
0.0%
L3
F . M O D
FORCED MANUAL OUTPUT MODE
Selects how the loop behaves on
transfer from Auto to Manual.
Transfer from Manual to Auto is always
bumpless.
none
Transfer between Auto/Manual/Auto is
bumpless
none
L3
SteP
Transfer from Auto to Manual, the
output goes to a pre-set value (F.OP)
Last
Transfer from Auto to Manual, the
output goes to the previously set
manual value
C o o l . t
NON-LINEAR COOLING TYPE
This selects an algorithm most suited to
the type of cooling. Typically used in
extruders.
Lin
Linear
Conf
OIL
Oil cooling
H20
Water cooling
Fan
Forced air cooling
F . O P
FORCED OUTPUT
To pre-set a value for the Manual output
when F.MOD = STEP
-100.0 to 100.0% limited by OP.HI and OP.LO
0.0
L3
A - M
LOOP MODE – AUTO MANUAL OFF
Auto
To select automatic operation
L3
Man
To select manual operation
OFF
Control outputs inhibited
l b r
LOOP BREAK STATUS
No
Shows the current status of loop break.
Read
only
YES
T U . H I
TUNE HIGH LIMIT. Set this to limit the
maximum heating output during
autotune
Range between OP.HI and OP.LO
+100.0
L3
T U . L O
TUNE LOW LIMIT. Set this to limit the
maximum cooling output during
autotune
Parameters are further described in the following sections.