2 control parameters, Control parameters – Super Systems 3 Series User Manual
Page 46

Operations Manual
Series 3
46
11.2
Control Parameters
The control loop is configured by the parameters listed in the following table:
CONTROL LIST
‘CTRL’
Parameter
Name
Parameter Description
(Scrolling Display)
Value
Default
Access
Level
C T R L . H
HEATING TYPE
Selects the channel 1 control algorithm.
Different algorithms may be selected
for channels 1 and 2. In temperature
control applications, Ch1 is usually the
heating channel, Ch2 is the cooling
channel.
Pid
PID
Conf
off
Heating off
on.of
On/Off
MTr
Valve position control (n/a)
C T R L . C
COOLING TYPE
Selects the channel 2 Control
algorithm. Different algorithms may be
selected for channels 1 and 2.
This is not available if the instrument is
a valve position controller
oFF
Cooling disable
Conf
pid
PID
on.of
On/Off
C T R L . A
CONTROL ACTION
Selects the direction of the control. i.e
reverse or direct acting.
rev
Reverse acting. Output decreases as
PV increases
rev
Conf
dir
Direct acting. Output increases as PV
decreases
P B . U N T
PROPORTIONAL BAND UNITS
enG
In engineering units
Perc
In percent
A T U N E
AUTO-TUNE ENABLE
OFF
Auto-tune off
OFF
L3
On
Set to ‘on’ to start auto-tuning
FaiL
Displayed if Autotune cannot be
completed
A T . R 2 G
AUTOTUNE CONFIGURES R2G
YES
R2G will be set by Auto-tune
yes
Conf
No
Allows a value for R2G to be entered
manually
P B
PROPORTIONAL BAND
0.1 to 9999 display units or
1 to 999.9% if proportional band expressed as %
20
L3
T I
INTEGRAL TIME
Off
to 9999 seconds
360
sec
L3
T D
DERIVATIVE TIME
Off
to 9999 seconds
TD
defaults to OFF for valve position control
60
sec
L3
R 2 G
RELATIVE COOL GAIN
0.1 to 10.0
1.0
L3
C B H i
CUTBACK HIGH
Auto
or 1to 3000 display units
Auto
=
3xPb
L3
C B L o
CUTBACK LOW
Auto
or 1 to 3000 display units
Auto
=
3XPb
L3
M R
MANUAL RESET
0.0 to 100.0% (heat only)
-100.0 to 100.0% (heat/cool)
0.0%
L3
L B T
LOOP BREAK TIME
The loop break alarm attempts to
detect loss of restoring action in the
control loop by checking the control
output, the process value and its rate of
change.
Loop break detection works for all
control algorithms: PID, VP and ON-
OFF.
Note: This is not to be confused with
load failure and partial load failure.
Off
Setting loop Break Time to OFF
disables the Loop Break Alarm
OFF
L3
1 to 9999 minutes
O P . H I
OUTPUT HIGH
Adjust to limit the maximum heating
power applied to the process
+100.0%
100.0%
L3