6 level 1 operator parameters, Operator level 2, 1 to enter level 2 – Super Systems 3 Series User Manual
Page 21: 2 to return to level 1, 3 level 2 parameters, Level 1 operator parameters, To enter level 2, To return to level 1, Level 2 parameters

Series 3
Operations Manual
21
4.4.6
Level 1 Operator Parameters
A minimal list of parameters are available in operator Level
1 which is designed for day to day operation. Access to
these parameters is not protected by a pass code.
Press
to step through the list of parameters.
The
mnemonic of the parameter is shown in the lower display.
After five seconds a scrolling text description of the
parameter appears.
The value of the parameter is shown in the upper display.
Press
or
to adjust this value. If no key is pressed
for 30 seconds the controller returns to the HOME display
The parameters that appear depend upon the functions
configured. They are:
Parameter
Mnemonic
Scrolling Display
and Description
Alterability
WRK.OP
WORKING OUTPUT
The active output
value
Read only.
Appears when the controller
is in AUTO or OFF mode.
WKG.SP
WORKING
SETPOINT
The active setpoint
value.
Read only.
Only shown when the
controller is in MAN or OFF
mode.
SP1
SETPOINT 1
Alterable
SP2
SETPOINT 2
Alterable
T.REMN
TIME REMAINING
Time to end of set
period
Read only
0:00 to 99.59 hh:mm or
mm:ss
A1.xxx
ALARM 1 SETPOINT Read only.
Only shown if the alarm is
configured.
xxx = alarm type as follows:
HI = High alarm
LO = Low alarm
d.HI = Deviation high
d.LO = Deviation low
d.HI = Deviation high
rrc = Rising rate of change
(units/minute)
Frc = Falling rate of change
(units/minute)
A2.xxx
ALARM 2 SETPOINT
A3.xxx
ALARM 3 SETPOINT
A4.xxx
ALARM 3 SETPOINT
LD.AMP
LOAD CURRENT
Read only. Only shown if CT
is configured
5. Operator Level 2
Level 2 provides access to additional parameters. Access to
these is protected by a security code.
5.1
To Enter Level 2
1. From any display press and hold
.
2. After a few seconds the display will
show
3. Release
.
(If no button is pressed for about 45 seconds the display
returns to the HOME display)
4. Press
or
to
choose Lev 2 (Level 2)
5. After 2 seconds the
display will show
6. Press
or
to enter the
pass code. Default = ‘2’
•
If an incorrect code is entered the controller reverts to
Level 1.
5.2
To Return to Level 1
1. Press and hold
2. Press
to select LEv 1
The controller will return to the level 1 HOME display.
Note: A security code is not required when going from a
higher level to a lower level.
5.3
Level 2 Parameters
Press
to step through the list of parameters.
The
mnemonic of the parameter is shown in the lower display.
After five seconds a scrolling text description of the
parameter appears.
The value of the parameter is shown in the upper display.
Press
or
to adjust this value. If no key is pressed
for 30 seconds the controller returns to the HOME display
Backscroll is achieved when you are in this list by pressing
while holding down
.
The following table shows a list of parameters available in
Level 2.