10 digital input parameters, Digital input parameters – Super Systems 3 Series User Manual
Page 41

Series 3
Operations Manual
41
9.1.10
Digital Input Parameters
Digital Input A. This is an optional input wired to terminals C and LA. The input is typically from a voltage free contact, which
can be configured to operate a number of functions as determined by parameters in the LA List.
Note: Terminal C is common to the CT input and is, therefore, not isolated from the CT.
Digital Input B. This is wired to terminals LB and LC.
The parameter lists for LB are identical as shown below:
LOGIC INPUT LIST ‘l a ’ / ‘LB’
Name
Scrolling Display
Parameter Description
Value
Default
Access Level
L.TYPE
LOGIC INPUT
TYPE
Input channel type
L.IP
Logic input
Conf
Read only
L.d.i n
LOGIC INPUT
FUNCTION
To configure the function of the
digital input
none
Input not used
Ac.AL
Conf
Ac.AL
Alarm acknowledge
SP2
Setpoint 2 select
Loc.b
Front keypad disable
Man
Manual status
Sby
Standby mode. In this mode control
outputs go to zero demand
rmt
To allow a remote setpoint to be
selected through the LA digital input.
UP
Remote key ‘Up’
dwn
Remote key ‘Down’
L.SENS
LOGIC INPUT
SENSE
To configure the polarity of the
input channel
nor
Normal
nor
Conf
Inv
Inverted