Super Systems 3 Series User Manual
Page 73

Series 3
Operations Manual
73
Parameter
Mnemonic
Parameter Name
Modbus Address
Decimal
-
Inverted Instrument Status. This is an inverted (bitwise) version of the preceding parameter and is provided so that scrolling
messages can be triggered when a condition is not active. Bit mappings are as the “Instrument Status”, Modbus address 75
76
LL.AMP
Load Leakage Current
79
LD.AMP
Load ON Current
80
A3.---
Alarm 3 Threshold
81
A4.---
Alarm 4 Threshold
82
LBT
Loop Break Time
83
F.OP
Forced manual output value
84
F.MOD
Forced manual output mode
0 – None
1 - Step
2 - Last
85
HYST.H
Ch1 On/Off Hysteresis in Eng Units
86
Di.IP
Digital Inputs Status. This is a bitmap:
B0 – Logic input 1A
B1 – Logic input LA
B2 – Logic input LB
B7 – Power has failed since last alarm acknowledge
A value of 1 signifies the input is closed, otherwise it is zero. Values are undefined if options are not fitted or not configured as
inputs.
87
HYST.C
Ch2 On/Off Hysteresis in Eng Units
88
FILT.T
Input Filter Time
101
RC.FT
Filter time constant for the rate of change alarm.
102
RC.PV
Calculated rate of change of the temperature or process variable in engineering units per minute.
103
Home
Home Display.
0 – Standard PV and SP display
1 – PV and Output Power display
2 – PV and Time remaining display
3 – PV
4 – FEATURE NOT AVAILABLE
5 – PV and Load Current
6 – PV only
7 – PV and Composite SP/Time remaining
8 – Target setpoint
9 – No PV
10 – PV is not displayed when controller in Standby
106
-
Instrument version number. Should be read as a hexadecimal number, for example a value of 0111 hex is instrument V1.11
107
SP.HI
Setpoint High Limit
111
SP.LO
Setpoint Low Limit
112
-
Instrument type code.
122
ADDR
Instrument Comms Address
131
PV.OFS
PV Offset
141
C.Adj
Calibration Adjust
146
IM
Instrument Mode
0 – Operating mode - all algorithms and I/O are active
1 – Standby - control outputs are off
2 – Config Mode - all outputs are inactive
199
MV.IN
Input value in millivolts
202
PV.CM
Comms PV Value. This may be used to write to the Process Variable (temperature) parameter over Modbus when a
linearisation type of ‘Comms’ is selected, allowing the instrument to control to externally derived values.
If sensor break is turned on, it is necessary to write to this variable once every 5 seconds. Otherwise a sensor break alarm will be
triggered as a failsafe. If this is not required, turn sensor break off.
203
CJC.IN
CJC Temperature
215
SBR
Sensor Break Status (0 = Off, 1 = Active)
258
NEW.AL
New Alarm Status (0 = Off, 1 = Active)
260
LBR
Loop Break (0 = Off, 1 = Active)
263
A.TUNE
Auto-tune Enable (0 = Off, 1 = Enabled)
270
A-M
Mode of the Loop (0 = Auto, 1 = Manual)
273
Ac.All
Acknowledge all alarms (1 = Acknowledge
274
L-R
Local Remote (Comms) Setpoint Select
276