beautypg.com

Temperature (or process) input, 1 process input parameters, Process input parameters – Super Systems 3 Series User Manual

Page 32: C with one decimal point

background image

Operations Manual

Series 3

32

8. Temperature (or Process) Input

Parameters in the input list configure the input to match your sensor. These parameters provide the following features:
Input Type and
linearisation

Thermocouple (TC) and 3-wire resistance thermometer (RTD) temperature detectors
Linear input (-10 to +80mV). 0-10V using external voltage divider. mA assumes a 2.49Ω external
shunt.
See the table in section 8.1.1. for the list of input types available

Display units and
resolution

The change of display units and resolution will all the parameters related to the process variable

Input filter

First order filter to provide damping of the input signal. This may be necessary to prevent the
effects of excessive process noise on the PV input from causing poor control and indication. More
typically used with linear process inputs.

Fault detection

Sensor break is indicated by an alarm message ‘Sbr’. For thermocouple it detects when the
impedance is greater than pre-defined levels; for RTD when the resistance is less than 12Ω.

User calibration

Either by simple offset or by slope and gain. See section 8.2. for further details.

Over/Under range

When the input signal exceeds the input span by more than 5% the PV will flash indicating under
or over range. If the value is too high to fit the number of characters on the display ‘HHHH’ or
‘LLLL’ will flash. The same indications apply when the display is not able to show the PV, for
example, when the input is greater than 999.9

o

8.1

Process Input Parameters

C with one decimal point.

INPUT LIST

I N P U T

Name

Scrolling Display

Parameter Description

Value

Default

Access Level

I N . T Y P

INPUT TYPE

Selects input linearisation and range

See section 8.1.1. for input types available

Conf
L3 R/O

U N I T S

DISPLAY UNITS

Display units shown on the
instrument

none

No units - only for custom linearisation

o

L3

C

o

Celsius

C

o

Fahrenheit

F

o

Kelvin

k

PErc

%

D E C . P

DISPLAY POINTS

Decimal point position

nnnn

No DP

nnnn

Conf
L3 R/O

nnn.n

One DP

nn.nn

Two DP

RNG.HI

RANGE HIGH
LIMIT

Range high limit for thermocouple
RTD and mV inputs

From the high limit of the selected input type to the
‘Low Range Limit’ parameter minus one display unit.

Conf
L3 R/O

RNG.LO

RANGE LOW
LIMIT

Range low limit for thermocouple
RTD and mV inputs

From the low limit of the selected input type to the ‘High
Range Limit’ parameter minus one display unit.

Conf
L3 R/O

PV.OFS

PV OFFSET

A simple offset applied to all input
values.
See section 8.2.

Generally one decimal point more than PV

L3

F I L T . T

FILTER TIME

Input filter time

OFF to 100.0 seconds

1.6

L3

C J . t y p

CJC TYPE

Configuration of the CJC type

Auto

Automa
tic

Auto

0

o

Fixed at
0

C

o

C

S B . t y p


SENSOR BREAK
TYPE


Defines the action which is applied
to the control output if the sensor
breaks (open circuit).
See also section 8.1.2

50

o

Fixed at 50

C

o

C

on

Conf and if
T/C
L3 R/O

oFF

No sensor break will be detected

on

Open circuit sensor will be detected

C J C . i n

P v . i n


CJC
TEMPERATURE
PV INPUT VALUE


Temperature measured at the rear
terminal block. Used in the CJC
calculation
Current measured temperature

Lat

Latching


Conf
L3 R/O
and if
T/C
Conf
L3 R/O

Conf
L3 R/O

Read
only

Minimu
m
display
to
maximu
m
display
range

m v . i n

MILLIVOLT
INPUT VALUE

Millivolts measured at the rear PV
Input terminals

xx.xx mV - read only

Conf
L3 R/O