7 output list 2 (op-2), 8 output list 3 (op-3), Output list 2 (op-2) – Super Systems 3 Series User Manual
Page 39: Output list 3 (op-3)
![background image](https://www.manualsdir.com/files/806360/content/doc039.png)
Series 3
Operations Manual
39
9.1.7
Output List 2 (OP-2)
This is an optional normally open relay and is available on terminals 2A and 2B. The way in which this output operates is
determined by parameters in the OP- 2 List. OP2 beacon is operated from this output channel.
OUTPUT LIST 2 ‘op-2’
Name
Scrolling
Display
Parameter Description
Value
Default
Access Level
2 . i d
OUTPUT 2
TYPE
Output channel 2 hardware
type
reLy
Relay output
As
ordered
Read only
2.FUNC
FUNCTION
Output channel 2 function
If the instrument is ordered as
valve positioner (codes VC or
VP), only options available are ,
none, d.out, UP
, or dwn
Note: If output 2 is set to Up
ensure the other valve
position output is set to dwn
and vice versa
none
Disabled. If disabled no further parameters are
shown
As
ordered
Conf
d.out
Digital output
Heat
Heat output
CooL
Cool output
2.SRC.A
I/O 2 SOURCE A
These parameters only appear
when the channel function is a
Digital OP,
i.e. 2.FUNC = d.Out
Selects an event status to be
connected to the output
channel.
The output status is the result
of an OR of Src A, Src B, Src C,
and Src D
Up to four events can,
therefore, operate the output
none
No event connected to the output
none
Conf
AL1
Alarm 1 *
2.SRC.B
I/O 2 SOURCE B
AL2
Alarm 2 *
AL3
Alarm 3 *
2.SRC.C
I/O 2 SOURCE C
AL4
Alarm4 *
ALL.A
All alarms
2.SRC.D
I/O 2 SOURCE D
nw.AL
Any new alarm
Ct.AL
CT alarm, load, leak & overcurrent
Lbr
Loop break alarm
Sbr
Sensor break alarm
mAn
Manual status
rmt.F
Remote fail
Pwr.f
Power fail
prg.e
FEATURE UNAVAILABLE
2.SENS
SENSE
To configure the polarity of
output channel 2
nor
Normal
nor
Conf
* The mnemonic for the alarm will change depending upon the alarm configuration.
9.1.8
Output List 3 (OP-3)
This is a normally 4-20 or 0-20mA isolated dc output. The way in which this output operates is determined by parameters in the
OP- 3 List. OP3 beacon is operated from this output channel.
OUTPUT LIST 3 ‘op-3’
Name
Scrolling
Display
Parameter Description
Value
Default
Access Level
3 . i d
OUTPUT 3
TYPE
Output channel 3 hardware
type
nonE
Output not fitted
As ordered
Read only
dC.Op
0-20mA output See note 1
3.FUNC
FUNCTION
Output channel 3 function
If the instrument is ordered as
valve positioner (codes VC or
VP), only options available are ,
none, d.out, UP
, or dwn
Note: If output 3 is set to Up
ensure the other valve
position output is set to dwn
and vice versa
none
Disabled. If disabled no further
parameters are shown
d.out
Conf
Heat
Heat output
CooL
Cool output
w.sp
Working setpoint re-transmission
Shown if I/O 3 TYPE = dc.OP
Retransmission
pV
Process variable re-transmission
Op
Output re-transmission
Inv
Inverted
3.rng
DC OUTPUT
RANGE
DC output calibration.
Only shown if
3 . i d = dC.Op
4.20
4-20mA
4.20
Conf
0.20
0-20mA
Note 1: A DC output may require calibration.