3.2 expansion card “a” input configuration – RLE Falcon EM User Manual
Page 41

User Guide: Falcon FMS
FMS Configuration
www.rletech.com 970
484-6510
27
Individual Ground Type (digital in only): Defines the type of digital input as either Individual Ground
or Common Ground.
Individual Ground: used if the monitored input is a single relay contact and two contacts—
common and NO or NC—are accessible.
Common Ground: used if multiple relays are to be monitored that have the commons bussed or
tied together (only one common input connection) and only the NO or NC contacts are available
for each individual relay output. See the example below or refer to section 2-2 Falcon FMS Wiring
on page 4, for more information.
Example: Configure input channels 1–2 for Individual Ground, and configure input
channels 4–6 for Common Ground.
N.O.
Contact
(Closes on
Alarm)
P1
VDC
TB1
VDC
+ -
EXTERNAL
24VDC
+ +
Ch1
+ -
Ch2
+ -
Ch3
+ -
Ch4
+ -
TB2 Input 1-4
Ch5
+ -
Ch6
+ -
Ch7
+ -
TB3 Input 5-8
Ch8
+ -
EXTERNAL
GND
- -
TB4
NC NO C
RELAY 1
NC NO C
RELAY 2
N.C.
Contact
(Opens on
Alarm)
ON Bypass
ON Battery
Low Battery
UPS
Figure 3-7: NO/NC Wiring Example
BACnet Instance: The BACnet object identifier. It is a numerical code used to identify the input. This
code must be unique within the BACnet device.
BACnet Units: A numerical code used to assign engineering units to this BACnet Instance. Refer to the
BACnet standard for further information.
3-3.2 Expansion Card “A” Input Configuration
To configure Expansion Card A, select the desired input or relay from the Input and Relay Configuration
page; see Figure 3-4, pg. 22. While units will vary depending on individual configurations, Expansion Card
A is typically numbered 1.1–1.12, 2.1–2.12, etc.