RLE Falcon EM User Manual
Page 103
User Guide: Falcon FMS
EIA232 Interface
www.rletech.com 970
484-6510
89
Table 6-1: EIA232 Main Menu
COMMAND DESCRIPTION
FUNCTION
CA
Current Alarms
CA
displays all active alarms on the master unit. If alarms
are present, the System Status LED is red.
KA
Kill Alarms
KA
acknowledges all alarms and terminates all dial-out
communications and network Traps.
TI
Display
Date/Time
TI
displays the FMS current time and date.
AD
ADC Input
Values
AD
allows the user to examine the readings of the 4-20mA
inputs. These readings can be referenced during start-up to
verify gain and offset calculations. Data displayed depends
on the expansion card(s) installed.
MS
Modem Statistics
MS
provides a summary of all modem information.
NS
Network
Statistics
NS
displays network and EIA485 statistics including:
network packets received, packets transmitted, and errors.
SC
Main
Configuration
SC
displays a submenu that lists all items for system setup
and configuration.
DU
Dump Network
Packets
DU
dumps the headers of all network packets received and
sent. Only active until the next command is entered. This
item is for network debugging only and is not normally
enabled.
NT
Network Trace
NT
displays troubleshooting messages during the
processing of network packets. Only active until the next
command is entered. Network Trace is for network
troubleshooting only and is not normally enabled.
PING
PING
Allows user to PING another device on the network.
EX
Exit to
Bootloader
EX
is used to enter the Bootloader command section. The
unit will stop monitoring the inputs and allow firmware
updates to be loaded. To restore normal operation after
updating firmware, type run and press Enter on the
keyboard, or power the unit off and back on again.