beautypg.com

RLE Falcon EM User Manual

Page 113

background image

User Guide: Falcon FMS

Upgrading Firmware, Loading & Saving Configuration Data

www.rletech.com 970

484-6510

99

3. To save settings, log into the FMS (COM2) through HyperTerminal (Terminal Emulation

Program). Navigate to the Load/Save Configuration Data Menu (5) under the Main
Configuration Menu (SC).

4. Select option

1

from the Load/Save Configuration Data Menu followed by the Enter key. Then

select the Transfer/Receive File from the menu at the top of the HyperTerminal screen.

5. Specify the file location and select the 1K X-Modem receiving protocol. Then click on the

Receive/Start button and enter the Filename for the Configuration file.

6. Wait until the download is completed and enter

X

to exit the Load/Save Configuration Menu.

9-2.3 Loading Configuration Data via TFTP Client

1. Verify that your PC is connected to the FMS over the LAN and that port 69 is open between your

PC and the FMS.

2. Open your TFTP client. Configure the client as follows.

a) Host = Falcon IP Address
b) Port = 69
c) Block Size = 64, 128, 256, 512, or 1024
d) NOTE: The file must be sent in BINARY (not ASCII).

3. The file name of the configuration being loaded must contain the .cfg extension.

4. Send or PUT the file. After a few seconds, the TFTP software should indicate when it is

complete.

5. If the FMS Modbus is used and configured, the Modbus configuration file is loaded in a separate

file. Send or PUT the .mfg configuration file. The TFTP software should indicate when it is
complete.

6. Configurations are now loaded onto the replacement FMS. View the FMS webpages to verify that

the configurations are as expected.

9-2.4 Loading Configuration Data via EIA232 COM2 Port (X-Modem)

1. To load settings, log into the FMS (COM2) through HyperTerminal (Terminal Emulation

Program). Navigate to the Load/Save Configuration Data Menu (5) under the Main
Configuration Menu.

2. Select option

2

from the Load/Save Configuration Menu and press the Enter key. Then select

Transfer/Send File from the menu at the top of the HyperTerminal screen.

3. Select the 1K X-Modem protocol. Locate the correct configuration file under Filename (Browse),

select Open, and then select the Send button.

4. Wait until the Upload is completed and enter

X

to exit the Load/Save Configuration Menu.