MDE-4319E TopKAT™ Fuel Management System Installation Manual · August 2008

Page 85

Pump Control EXPMUX CPU Board

Mechanical PCU Option

An address must be set to identify the pump control unit when it is connected to the TopKAT
system. This address is a unique identifier for multiple PCUs that are connected on the same
RS-485 line. Addressing should start at 1 and continue sequentially through 16. The physical
wiring order does not have to correspond with the address order, that is, the first unit on the
RS-485 line does not have to be address 1.

Switches 1 through 4 denote the address. This is factory set and does not have to be corrected.
The table below provides the switch settings for the address selections.

Address

SB-1

SB-2

SB-3

SB-4

ADDR1

ADDR2

ADDR3

ADDR4

1

Closed

Closed

Closed

Closed

2

Open

Closed

Closed

Closed

3

Closed

Open

Closed

Closed

4

Open

Open

Closed

Closed

5

Closed

Closed

Open

Closed

6

Open

Closed

Open

Closed

7

Closed

Open

Open

Closed

8

Open

Open

Open

Closed

9

Closed

Closed

Closed

Open

10

Open

Closed

Closed

Open

11

Closed

Open

Closed

Open

12

Open

Open

Closed

Open

13

Closed

Closed

Open

Open

14

Open

Closed

Open

Open

15

Closed

Open

Open

Open

16

Open

Open

Open

Open

8

Switches SB-5 through SB-8 are not relevant to the operation of this unit and should be set to
Closed.

9

The settings for switch bank SC (1 through 4) determine when the pump control unit begins
counting pulses for a particular pump. When a switch is open, the PCU begins counting pulses
when the corresponding pump is activated. When a switch is closed, as it should be for most
configurations using mechanical pumps, the PCU does not count pulses for the corresponding
pump until the mechanical reset has completed. The table below provides the switch settings
for SC-1 through SC-4.

Switch

Function

SC-1

Mode pump 1

Open = Normal, Closed = Reset Complete

SC-2

Mode pump 2

Open = Normal, Closed = Reset Complete

SC-3

Mode pump 3

Open = Normal, Closed = Reset Complete

SC-4

Mode pump 4

Open = Normal, Closed = Reset Complete