Gasboy TopKAT Fuel Management System Installation User Manual
Page 57
MDE-4319E TopKAT™ Fuel Management System Installation Manual · August 2008
Page 51
Wiring Diagrams
Mechanical Interface Option
4) When installed in a separate DC conduit, 18 AWG wires are required for
installation. Although it is recommended that DC pulser wires be run in a separate
conduit away from AC wires, they can be combined in the same conduit with AC
wires if UL-listed cable with the following specifications is used:
• Conductor: 18 AWG stranded wire. Number of conductors to be determined by the
pulser
• Shield: Foil-wrapped 100% coverage and/or tinned copper braid 90% coverage
• Drain Wire: Stranded, tinned copper, 20 AWG or larger/or braided shield
• Voltage Rating: Maximum operating voltage of 600 VDC
• Environmental: Gas and oil-resistant; suitable for wet or dry locations.
Gasboy can supply Belden 1063A (part number C09655) which is a UL-listed, 4-conductor
cable that meets the requirements listed above.
Note: Belden 1063A is UL-listed but not CSA-listed.
Figure 7-6: Wiring Diagram: Single Suction Pump, 115 VAC/230 VAC, Veeder-Root
Reset