Pulser wiring notes – Gasboy TopKAT Fuel Management System Installation User Manual
Page 100
![background image](https://www.manualsdir.com/files/787529/content/doc100.png)
Mechanical PCU Option
Wiring Diagrams: Pulsers, Pumps, Dispensers
Page 94
MDE-4319E TopKAT™ Fuel Management System Installation Manual · August 2008
Pulser Wiring Notes
Notes: 1) All the pulsers shown above are connected to Hose 1.
2) Jumpers on the Pump Control PCB must be properly jumpered according to the
pulser type. This should be done by the person performing the start-up. Power to the
system must not be turned on prior to this setup.
“Conduit Layout/Installation Specifications”
for detailed system
installation specifications.
4) When installed in a separate DC conduit, 18 AWG wires are required for
installation. Although it is recommended that DC pulser wires be run in a separate
conduit away from AC wires, they can be combined in the same conduit with AC
wires providing UL-listed cable with the following specifications is used:
• Conductor: 18 AWG stranded wire. Number of conductors to be determined by
pulser
• Shield: Foil-wrapped 100% coverage and/or tinned copper braid 90% coverage
• Drain Wire: Stranded, tinned copper, 20 AWG or larger/or braided shield
• Voltage Rating: Maximum operating voltage of 600 V
• Environmental: Gas- and oil-resistant; suitable for wet or dry locations.
Gasboy can supply Belden 1063A (part number C09655) which is a UL-listed, 4-conductor
cable that meets the requirements listed above.
Note: Belden 1063A is UL-listed but not CSA-listed.