Pulser wiring notes – Gasboy TopKAT Fuel Management System Installation User Manual

Page 100

background image

Mechanical PCU Option

Wiring Diagrams: Pulsers, Pumps, Dispensers

Page 94

MDE-4319E TopKAT™ Fuel Management System Installation Manual · August 2008

Pulser Wiring Notes

Notes: 1) All the pulsers shown above are connected to Hose 1.

2) Jumpers on the Pump Control PCB must be properly jumpered according to the

pulser type. This should be done by the person performing the start-up. Power to the
system must not be turned on prior to this setup.

3) Refer to

“Conduit Layout/Installation Specifications”

on

page 14

for detailed system

installation specifications.

4) When installed in a separate DC conduit, 18 AWG wires are required for

installation. Although it is recommended that DC pulser wires be run in a separate
conduit away from AC wires, they can be combined in the same conduit with AC
wires providing UL-listed cable with the following specifications is used:

• Conductor: 18 AWG stranded wire. Number of conductors to be determined by

pulser

• Shield: Foil-wrapped 100% coverage and/or tinned copper braid 90% coverage
• Drain Wire: Stranded, tinned copper, 20 AWG or larger/or braided shield
• Voltage Rating: Maximum operating voltage of 600 V
• Environmental: Gas- and oil-resistant; suitable for wet or dry locations.

Gasboy can supply Belden 1063A (part number C09655) which is a UL-listed, 4-conductor
cable that meets the requirements listed above.
Note: Belden 1063A is UL-listed but not CSA-listed.