beautypg.com

Submersible feed, submersible drive, Reset complete (switch detect), Light feed – Gasboy TopKAT Fuel Management System Installation User Manual

Page 51: Light neutral, Phase 2 feed, Pulser - mechanical pump

background image

MDE-4319E TopKAT™ Fuel Management System Installation Manual · August 2008

Page 45

Control Lines for Mechanical Pumps/Dispensers

Mechanical Interface Option

Submersible Feed, Submersible Drive

This is a 115 VAC input which is supplied to the input side of one of the internal switches of
the electric reset. This line must be switched through the TopKAT system and only be on
when the pump/dispenser is authorized or in Manual mode. When the reset finishes its cycle,
the 115 VAC input to the switch is passed through as an output (submersible drive) to drive a
starter relay or to directly drive a submersible motor up to 3/4 HP at 115 VAC or 1-1/2 HP at
230 VAC. Any submersible motor exceeding this limitation must use a starter relay.

Note: 230 VAC is developed across a motor when the other leg of the motor is connected to a

Phase 2 Feed.

Reset Complete (Switch Detect)

This is a 115 VAC output which is used to indicate the reset is complete and the pump/
dispenser is ready to dispense the product. Two lines are provided for twins. This line must
only be used when monitoring of the pump/dispenser is desired (for example, when used with
a fuel management system). This line must be capped when not in use.

Light Feed

This is a 115 VAC input required to power optional fluorescent lights that may be available in
a pump/dispenser. In a site configuration using multiple dispensers (or pumps), the power for
the lights of up to eight units can be supplied by one breaker. The light feed is not controlled
by the TopKAT system.

Light Neutral

This is a return line for AC current from the lights to the breaker panel.

Phase 2 Feed

This is a hot feed which is the opposite phase of the pump motor feed. This line and the pump
motor feed are used for 230 VAC motor applications.

Pulser - Mechanical Pump

This supplies a DC output which is provided to indicate the quantity dispensed.