MDE-4319E TopKAT™ Fuel Management System Installation Manual · August 2008

Page 29

Port Communication Wiring

Series 9820 ASTRA Installation

Figure 5-6: RS-232 - Gasboy Termination Box

1

1

2

3

4

5

1

2

3

4

5

TopKAT

PORT 2 OR 3

RS-232

100 FEET MAX

P/N C05769

EIA 1:1 CABLE

P/N C04549

MODEM CABLE

P/N C05039

CRT OR PC

ANSWER ONLY
EXTERNAL MODEM

TXD

DTR

RXD

CD

GND

GASBOY
RS-232

Note: In the TopKAT system, the green connector must be connected to P4 on the

communication board for Port 2, and P6 for Port 3. The K1 and K2 jumper for the port
being used should be set to RS-232. Refer to

“Terminal Block ID”

on

page 24

for the

location of K1 and K2 jumpers.

Figure 5-7: RS-422 - Gasboy Short Haul Modem

Notes:1) In the TopKAT system, the green connector must be connected to P3 on the

communication board for Port 2 and P5 for Port 3.

2) If a TopKAT internal modem is used, Port 3 is not available for external

communication wiring.

3) The K1 and K2 jumper for the port being used should be set to RS-422. Refer to

“Terminal Block ID”

on

page 24

for the location of K1 and K2 jumpers.