Gasboy TopKAT Fuel Management System Installation User Manual
Page 134
Testing
Manual Override Test - 4-hose Mechanical PCU Option
Page 128
MDE-4319E TopKAT™ Fuel Management System Installation Manual · August 2008
7
Turn off all hoses.
8
Place the system override switches for hose 1 in the ON position.
9
Repeat steps
for all remaining hoses. Substitute the hose under test for hose 1.
10
Turn off the AC power and battery power switches in the PCU.
11
Turn off the breakers for all the pumps and/or remote dispensers and the TopKAT system and
other components.
12
Replace all wiring connectors (green) removed in step
assembly.
Note: The manual override test will uncover most point-to-point AC wiring mistakes that can
occur. The automatic test performed during the system start-up will complete the
verification of correct AC wiring to the pimp/remote dispensers. The automatic test
should only be performed at start-up.