Mounting, Ounting – Comtech EF Data LCS-4 User Manual

Page 22

background image

LCS-4 L-Band Combiner Switch

Revision 1

Installation

MN/LCS4.IOM

2.2

M

OUNTING

If the LCS-4 is to be mounted in a rack, ensure that there is adequate clearance for
ventilation, particularly at the sides. In rack systems where there is high heat dissipation,
forced air-cooling must be provided by top and bottom mounted fans or blowers.
UNDER NO CIRCUMSTANCE should the highest internal rack temperature be
allowed to exceed 50

°C (122° F).


Install optional installation bracket (Figure 2-1) using mounting kit, KT/6228-1.

Optional: Mounting Kit, KT/6228-1

Quantity

Part Number

Description

2 FP/6138-1

Bracket,

Rear

Support

4

HW/10-32x1/2RK

Bolt, #10 Rack

2 HW/10-32HEXNUT

Nut,

#10

Hex

2 HW/10-32FLT

Washer,

#10

Flat

2

HW/10-32x1/4SHC

Screw, Socket 10-32 x 1/4inch

The tools required for this installation are a medium Phillips

 screwdriver and a 5/32-

inch SAE Allen Wrench

.


Refer to the Figure 2-1, and then install the LCS-4 rear support brackets as follows:

1. Install the rear support brackets onto the mounting rail of the rack. Fasten with

the bracket bolts.

2. Mount the LCS-4 into the equipment rack ensuring that the socket heads

engage into the LCS-4 slots of the rear support brackets,

3. Fasten the provided #10 socket head screws to the rear-side mounting slots on

either side of the chassis and secure with #10 flat washers and #10 hex nuts.
















2–2