Section 3: Appendixes

removeapp index|name

Deletes an existing application instance, specified by index or name.
The user should generally not use this command.

rename file1 file2

Renames file1 to file2.

servicepin index

Sends a service pin message for the application specified by index.
See activateapp for supported indexes.

show [all|
hwInfo

]

This displays configuration information about the i.LON 600 server.
For example, show might display:
Software Version:

2.00-0024

IP Address:

10.1.253.201

Subnet Mask:

255.0.0.0

Host Name:

echeloni600

Gateway: 0.0.0.0
SNTP Server:

0.0.0.0

DHCP: off
MAC Address:

00-D0-71-00-4A-04

Time:

MON SEP 13 08:30:02 2003

UTC Time:

MON SEP 13 06:30:02 2003

Startup script:
/root/config/startup.scr
Timezone: MET:60:1:5.1.3.2:5.1.10.4
Show all displays all parameters. Show hwinfo displays hardware
properties.

shutdown

Quits all applications on the i.LON 600 device. A reboot is required to
restore operation of all modules.

sntpaddress address

Modifies the address of the SNTP server. If you have a backup SNTP
server, you can enter sntpaddress address1 address2.

sntplog on|off

Enables or disables SNTP logging. The SNTP log file is named
sntp.log and is located in the root directory of the i.LON 600

server. The time logged in the SNTP log file is in universal coordinated
time (UTC). The maximum size of the SNTP log file is 50 Kbytes.
When the file exceeds 50 Kbytes, logging is automatically disabled.
Use this command to diagnose time synchronization problems.

subnetmask address

Modifies the subnet mask. For example, subnetmask
255.255.255.0. This command is valid only when DHCP is turned

off.

time hh:mm:ss

Sets the time. This is not allowed if the i.LON 600 server is synched to
an SNTP server.

timezone zone

Sets the time zone with the following format:
nameOfZone:timeInMinutesFromUTC:dstUsed:daylightStar
t
:daylightEnd where dstUsed is 0 or 1, and daylight savings
start/end times are in the form rank.day.month.hour. For

example, 1.1.4.2 is the first Sunday in April at 02:00. Rank is a number
from 1 to 5 with 5 meaning the last instance in the month. Days are
numbered 1 to 7 starting with Sunday. Months are numbered 1 to 12,
starting with January.

trace level [stamp]

Sets the tracing level; 0 = None; 1 = Urgent tracing only (default); 2 =
Verbose tracing (for debugging only, not recommended). The optional
stamp

parameter enables time stamping with each trace.

type file

Types the contents of file.

update bootrom [file]

Updates the bootrom of the i.LON 600 server. By default, this
command will look for the bootrom.upd file in the /root directory of

the i.LON 600 server. Echelon highly recommends that user run this
command from the i.LON 600 bootrom console. See
Interrupting the Boot

Process, later in this Appendix, for more

information.

94

i.LON 600 Console Application