A. Preliminary Information

OUTDOOR: MODEL NO.

START-UP CHECKLIST

SERIAL NO.

INDOOR: AIR HANDLER MANUFACTURER.

MODEL NO.___________________

ADDITIONAL ACCESSORIES________________

SERIAL NO.

o

c

>

r~

o

z

O

D

Q

m

O

o

c:

O

z

Q

O

O

m

D

z

m

B, Pre-Start-Up

OUTDOOR UNIT

IS THERE ANY SHIPPING DAMAGE?

IF SO, WHERE:______________________

(Y/N)

WILL THIS DAMAGE PREVENT UNIT START-UP? (Y/N)_________________

CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT?

(Y/N)_______

HAS THE GROUND WIRE BEEN CONNECTED? (Y/N)_________________

HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY?

(Y/N)

ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY?

(Y/N)

HAVE COMPRESSOR HOLDDOWN BOLTS BEEN LOOSENED? (Y/N)__________________

CONTROLS

ARE THERMOSTAT(S) AND INDOOR FAN CONTROL WIRING

CONNECTIONS MADE AND CHECKED? (Y/N)________________

ARE ALL WIRING TERMINALS (including main power supply) TIGHT? (Y/N)___________________

HAVE CRANKCASE HEATERS BEEN ENERGIZED FOR 24 HOURS? (Y/N)___________________

INDOOR UNIT

HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE? (Y/N)_____________________

ARE PROPER AIR FILTERS IN PLACE? (Y/N)________________

HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT? (Y/N)_____________________

DO THE FAN BELTS HAVE PROPER TENSION? (Y/N)_________________

PIPING

ARE LIQUID LINE SOLENOID VALVES LOCATED AT THE EVAPORATOR COILS AS REQUIRED? (Y/N)

HAVE LEAK CHECKS BEEN MADE AT COMPRESSORS, CONDENSERS, EVAPORATORS,

TXVs (Thermostatic Expansion Valves) SOLENOID VALVES, FILTER DRIERS, AND FUSIBLE PLUGS
WITH A LEAK DETECTOR? (Y/N)_______________

LOCATE, REPAIR, AND REPORT ANY LEAKS----------------------------------------------------------------------------------------------------------

HAVE ALL COMPRESSOR SERVICE VALVES BEEN FULLY OPENED (BACKSEATED)? (Y/N)____________________

ARE THE COMPRESSOR OIL SIGHT GLASSES SHOWING ABOUT Va FULL? (Y/N)____________________

AC

CHECK VOLTAGE IMBALANCE

LINE-TO-LINE VOLTS:

AB________ V

(AB + AC + BC)/3 = AVERAGE VOLTAGE =_______________

MAXIMUM DEVIATION FROM AVERAGE VOLTAGE =

BC

V

VOLTAGE IMBALANCE = 100 X (MAX DEVlATION)/(AVERAGE VOLTAGE) =__________

IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!
CALL LOCAL POWER COMPANY FOR ASSISTANCE.

%

CL-1