beautypg.com

38ан124,134, A caution, Caution – Carrier 38AH044-134 User Manual

Page 31: Lb2j

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

38АН124,134

MODULE

124А OR 134A

ТВЗ

Ф

TIME

GUARD®
CONTROL

SDR2 ^

CCPS -ÆA^

MODULE

124B OR 134B

ACCESSORY

RELAY
PACKAGE

CR1

—^—II—vio

CR2

TB3

TIME

GUARD®
CONTROL

SDR2 ^

—It—^

CCPS

SDR2

;cAi

'CA2]

SDR2

|] Щ И

L

j

U_SEE

NOTE 2

_____ I

|T

ls

1

I

T

lls

I

LB2j

I___ I

-

yel

A

CAUTION

Internal TSR-01 relay contacts are rated for 1 amp/24 vac.

q

-COMMUNICATION

OUT

- COMMUNICATION IN

CARRIER COMMUNICATING
TEMP MONITOR THERMOSTAT

.(MODEL MS(T)01ES)

++-WHtTE--

e

«ED— e

BLUE— e

____YELLOW- e

-- - — OREEN--

REMOTE ROOM

TEMP SENSOR

•Jumper removed only when separate 24-v transformer power

source is used to power the TSR-01 relay pack

TSR-01 RELAY PACK CIRCUIT BOARD

-----------

fan

"I

1

HEAT 2 -i

-------- HEAT 1 -5

0

'■--------- COOL2-------------‘ I

------- COOL1---------------- '

" —"________ J

I —24 VAC (R)

24 VAC (Comrtran)

NOTES:

1 Liquid line solenoid valves LLS-A1 and A2 are used for

solenoid drop on Module 124A or 134Aon circuit A Liq­
uid line solenoid valves LLS-B1 and B2 are used for

solenoid drop for Module 124B or 134B. Solenoid drop

is a safety feature which prevents refrigerant migration

to the compressor during the OFF cycle It is recom­

mended on all systems and required on systems where
piping exceeds 75 ft (22 9 m) in length

2

Disconnect black wire from CR2 terminal 6; cap loose

end and secure Connect new field-supplied wire from

CR2 terminal 6 to ТВЗ terminal 1 on module 124B or

134B

3 The TSR-01 relay pack requires 10 va
4

Factory wiring is in accordance with NEC; field modi­

fications or additions must be in compliance with all ap­
plicable codes

5 Wiring for field power supply must be rated 75 C mini­

mum Use copper, copper-clad aluminum, or alumi­

num conductors Maximum incoming wire size for each
terminal block is 500 kcmil.

6. Terminal blocks (ТВЗ) are for external field control con­

nections Control connections must be class 1 wiring

10

Field-supplied

components

{IFC,

LLS-A1,A2,

and

LLS-B1 ,B2) must have a maximum sealed coil rating
of 30 va each (0 25 amp at 120 vac and 0 13 amp at

230 vac) Thermostats must have a minimum pilot cluty

rating of 300 va (2 5 amps at 120 vac)
Replacement of factory wires must be with type 105 C

wire or its equivalent.
Field-supplied liquid line solenoid valves installed at the
evaporator are required on all units

Units have 175 va of power available for field-installed

accessories.

To minimize voltage drop, the following wire sizes are

recommended:

LENGTH —

Ft(M)

INSULATED WIRE — AWG

(35 C Minimum)

Up to 50

(15.2)

No 18

50-75
(15.2-22.9)

No 16

More Than 75
(22.9)

No 14

LEGEND

AWG

— American Wire Gage

C

— Compressor Contactor

CCPS

— Capacity Control Pressure

Switch

CR

— Control Relay

HD

— Heating Device

IFC

— Indoor-Fan Contactor

IFR

— Indoor-Fan Relay

kcmil

— Thousand Circular Mils

LLS

— Liquid Line Solenoid

NEC

— National Electrical Code

(U S.A Standard)

R

— Heating Relay (field-

supplied 24-v sealed coil,

10 va maximum rating)

RV

— Reversing Valve

SDR

— Solenoid Drop Relay

TB

— Terminal Block

TR

— Timer Relay

Factory Wiring

------------- Field Wiring

Fig. 23 — Field Wiring, One 2-Stage Thermostat — Units 38AH124 and 134

31