Table 7A — Refrigerant Piping Requirements, 38AH044-104 Dual-Circuit Units — 50 Hz
TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE — FT (M)
UNIT
15-25
25-50
50-75
75-100
100-150
150-200
38AH
(4.6-7.6)
(7.6-15.2)
(15.2-22.9)
(22.9-30.5)
(30.5-45.7)
(45.7-61.0)
L
S
L
S
L
s
L
s
L
s
L
s
044
Ckt A
%
1%
%
1%
%
1%
%
2У8
Va
2Уе
Va
2У8
Ckt В
%
1%
%
1%
Va
1%
Va
2У8
Va
2Va
Va
2У8
054
Ckt A
%
1%
Va
1%
Va
1%
Va
2Уб
Va
2Va
Va
2У8
Ckt В
%
Wa
Va
1%
Va
2У8
Va
2Уа
^Va
2Va
1У8
2%*t
064
Ckt A
%
Wa
Va
1%
Va
2yst
Va
2Va\
V/a
2Va\
1У8
2%”
Ckt В
%
1%
Va
2У8
Va
2Ув
Va
2Va
V/a
2%*
' 1У8
2%’
074
Ckt A
%
1%
Va
2Уа
Va
2Ув
Va
2Va
^Va
2%t
1У8
2%t
Ckt В
%
2Ув
Va
2Уб
1У8
2Ув
1У8
2%
V/a
2%
1У8
2%
084
Ckt A
%
2Va
Va
2Ув
1У8
2Ув
1У8
2%t
1У8
2Щ
1У8
2%t
Ckt В
%
2Va
Va
2Ув
1Ув
2У8
1Уа
2%
1У8
2%
1У8
2%
094
Ckt A
%
2Va
IVe
2Ув ^
1У8
2%”
1У8
2%”
1У8
2%”
1%
ЗУв”
Ckt В
%
2Va
%
2Уе
1У8
2У8
1У8
2¥8*t
1У8
2%*t
1У8
2%’t
104
Ckt A
%
2Va
Va
2Ув
1У8
2Уа
1У8
2%”
1У8
2У8**
1%
ЗУе”
Ckt В
%
2Va
1У8
2Ув
1У8
2%
1У8
2Va
1%
2%
1%
ЗУ8”
i.
LEGEND
CV
— Constant Volume
L
— Liquid Line
S
— Suction Line
VAV
— Variable Air Volume
’Double suction riser required on units with field installed unloader
on circuit B compressor if condensing unit is elevated above
evaporator.
TDouble suction riser required on units with field installed unloader
on circuit B compressor if condensing unit is elevated above
evaporator.
’’Double suction riser required on all unit configurations if condens
ing unit is elevated above evaporator
NOTES-
1
Addition of 2 unloaders to circuit B compressor is not
recommended
2. 38AH094 and 38AH104 piping sizes apply only to factory sup
plied unit configurations They do NOT take into account any field
installed unloaders
3
Piping sizes are based on unit operation above 40 F (4 4 C) satu
rated suction temperature (SST) When operating below 40 F
(4 4 C), refer to Carrier System Design Manual, E20-II piping de
sign program, or ASHRAE Handbook to select proper line sizes
4
Pipe sizes are based on the total linear length shown for each
column, plus a 50% allowance for fittings
5.
Suction and liquid line sizing is based on pressure drop equivalent
to 2 F (1 1 C) at nominal rating conditions. Higher pressure drop
design criteria may allow selection of smaller pipe sizes, but at a
penalty of decreased system capacity and efficiency
6
Double suction risers may be required if condensing unit is el
evated above the evaporator See footnotes and double suction
riser table below
7
Refer to Carrier System Design Manual or to E20-II design
programs for further information on selecting pipe sizes for split
systems
8
All pipe sizes are OD inches Equivalent sizes in millimeters
follow
in.
mm
Va
159
Va
22 2
V/a
28 6
V/a
34 9
V/a
41 3
2Va
54 0
2Va
66.7
ЗУ8
79 4
ЗУ8
92 1
Table 7B— Refrigerant Piping Requirements for Double Suction Risers,
38AH054-104 Dual-Circuit Units — 50 Hz
TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE — FT (M)
UNIT
50-75
75-100
100-150
150-200
38AH
15.2-22.9)
(22.9-30.5)
30.5-45.7)
45.7-61.0
A
В
C
A
В
С
А
В
С
А
В
С
054
Ckt A
Ckt В
___
___
—
___
—
___
—
—
___
V/a
2Уа
25/8
064
Ckt A
1%
V/a
2У8
V/a
V/a
2Ув
15/8
15/8
2У8
V/a
2Уа
25/8
Ckt В
—
—
—
—
—
—
15/8
2Уа
25/8
V/a
2Уа
25/8
074
Ckt A
Ckt В
___
___
—
___
___
___
15/8
2Уа
25/8
V/a
2Уа
25/8
084
Ckt A
Ckt В
___
___
—
V/a
2У8
25/8
15/8
2Уа
25/8
V/a
2Уа
25/8
094
Ckt A
V/a
2Vs
2%
V/a
2Уз
25/8
15/s
2Уа
25/8
V/a
25/8
ЗУз
Ckt В
—
—
—
V/a
2Ув
25/8
15/8
2Уа
25/8
V/a
2У8
25/8
104
Ckt A
—
—
—
V/a
2Уе
25/8
15/8
2Уа
25/8
V/a
25/8
ЗУб
Ckt В
—
—
—
—
—
—
—
—
—
V/a
25/8
ЗУ8
LEGEND
—
— Not Required
Pipe A
— Suction Riser Without Trap
Pipe B
— Suction Riser With Trap
Pipe C
— Suction Line to Condensing Unit
NOTES:
1 See Refrigerant Piping Requirements table at top of page to de
termine need for double suction risers
2 Pipe sizes are based on the total linear length, shown for each
column, plus a 50% allowance for fittings.
3.
4.
Suction and liquid line sizing is based on pressure drop equivalent
to 2 F (1 1C) at nominal rating conditions. Higher design pressure
drop criteria may allow selection of smaller pipe sizes but at a pen
alty of decreased system capacity and efficiency.
Refer to Carrier System Design Manual or to E20-II design
programs for further information on selecting pipe sizes for split
systems
All pipe sizes are OD inches. See Table 7A notes for metric
equivalents
Refer to Fig. 13 for double suction riser construction
17