Carrier 38AH044-134 User Manual
Page 18
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Table 8A — Refrigerant Piping Requirements for 38AH044-084 Optionai Single-Circuit Units and
38AH124,134 Modular Units (Duai-Circuit) — 60 Hz
TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE — FT (M)
UNIT 38AH
15-20
(4.6-6.1)
20-50
(6.1-15.2)
50-75
(15.2-22.9)
75-100
(22.9-30.5)
100-150
(30.5-45.7)
150-200
(45.7-61.0)
L
s
L
s
L
s
L
s
L
S
L
S
044
%
2V8
%
2Ув
1У8
2Уа
1У8
2%*
1%
2%*
1%
ЗУ8*
054
%
2У8
1У8
2%
1У8
2%
1У8
2%
1%
ЗУ8*
1%
ЗУ8*
064;
Modules 124A,
1248,134A
1У8
2У8
1У8
2%t
1У8
2%t
1%
ЗУ8*
1%
ЗУ8*
1%
ЗУ8*
074;
Module 134B
1У8
2У8
1У8
2%t
1%
3V8t
1%
3yat
1%
ЗУв|
1%
3%*
084
IVe
2%t
1У8
2%t
1%
3Vsf
1%
31/8t
1%
3%t
1%
3%*
LEGEND
CV
— Constant Volume
L
— Liquid Line
S
— Suction Line
VAV
— Variable Air Volume
‘Double suction riser required on all units configurations if condens
ing unit is elevated above evaporator.
tDouble suction riser required on units with factory installed VAV op
tion or CV units with additional field installed unloader on circuit A1
Oead) compressor if condensing unit is elevated above evaporator
NOTES;
1 Addition of field-installed unloaders on A2 (lag) compressor is not
recommended
2. Piping sizes are based on unit operation above 40 F (4.4 C) satu
rated suction temperature (SST). When operating below 40 F
(4 4 C), refer to Carrier System Design Manual, E20-II piping de
sign program, or ASHRAE Handbook to select proper line sizes
3.
Pipe sizes are based on the total linear length shown for each
column, plus a 50% allowance for fittings.
4 Suction and liquid line sizing is based on pressure drop equivalent
to 2 F (1 1 C) at nominal rating conditions Higher pressure drop
7.
design criteria may allow selection of smaller pipe sizes, but at a
penalty of decreased system capacity and efficiency
Double suction risers may be required if condensing unit is el
evated above the evaporator See footnotes and double suction
riser table below.
Refer to Carrier System Design Manual, E20-II design program,
or ASHRAE Handbook for further information on selecting pipe
sizes for split systems.
All pipe sizes are OD inches Equivalent sizes in millimeters
follow;
in.
mm
%
159
%
22 2
1У8
28 6
1%
34 9
1%
41 3
2Ув
54 0
2%
66.7
ЗУ8
79.4
3%
92 1
Table 8B — Refrigerant Piping Requirements for Double Suction Risers, 38AH044-084 Optional Single-Circuit
Units and 38AH124,134 Moduiar Units (Dual-Circuit) — 60 Hz
TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE — FT
UNIT 38AH
15-50
(4.6-15.2
50-75
(15.2-22.9)
75-100
(22.9-30.5)
100-150
(30.5-45.7)
150-200
(45.7-61.0)
A
В
С
А
В
С
А
В
С
А
В
С
А
В
С
044
—
—
—
—
—
—
1%
2Уа
2%
1%
2Уа
2%
1%
2%
ЗУе
054
—
—
—
—
—
—
—
—
—
1%
2%
ЗУа
1%
2%
ЗУа
064
Modules 124A,
124B,134A
1%
2Ув
2%
1У8
2У8
2%
1%
2%
ЗУа
15/а
2%
ЗУа
1%
2%
ЗУе
074;
Module 134B
1%
2Ув
2%
1%
2%
ЗУз
1%
2%
ЗУв
1%
2%
ЗУе
2У8
ЗУв
ЗУа
084
1%
2У8
2%
1У8
2%
ЗУа
1У8
2%
ЗУа
2Уа
ЗУа
3%
2Уа
ЗУе
ЗУ8
LEGEND
—
— Not Required
Pipe A
— Suction Riser Without Trap
Pipe B
— Suction Riser With Trap
Pipe C
— Suction Line to Condensing Unit
NOTES;
1 See Refrigerant Piping Requirements table at top of page to de
termine need for double suction risers.
2 Pipe sizes are based on the total linear length, shown for each
column, plus a 50% allowance for fittings.
3
Suction and liquid line sizing is based on pressure drop equivalent
to 2 F (1.1 C) at nominal rating conditions Higher design pressure
drop criteria may allow selection of smaller pipe sizes but at a pen
alty of decreased system capacity and efficiency
4.
Refer to Carrier System Design Manual or to E20-II design
programs for further information on selecting pipe sizes for split
systems
5
All pipe sizes are OD inches See Table 8A notes for metric
equivalents
6 Refer to Fig 13 for double suction riser construction
18