Table 11 — Electrical Data — 50/60 Hz (Units 38AH094,104)
UNIT
38AH
VOLTAGE
DESIGNATION
NAMEPLATE
V-Ph-Hz
SUPPLY
VOLTAGE*
MCA
MOCP
ICF
COMPRESSORt
A1
A2
B1
B2
Min
Max
RLA
LRA
RLA
LRA
RLA
LRA
RLA
LRA
094
500
208/230-3-60
187
253
398 5
500
897
106.4
506
67.9
345
147.7
690
—
—
600
460-3-60
414
506
183 1
225
443
46.8
253
34.6
173
65.4
345
—
—
100
575-3-60
518
633
160.9
200
366
40.4
176
28 8
120
57.1
276
—
—
200
380-3-60
342
418
209.1
250
493
52 6
280
34.6
191
78.8
382
—
—
900
380/415-3-50
342
440
183.6
225
444
46.8
280
34 6
173
65.4
345
—
—
300 (PW)
346-3-50
325
380
212 9
250
343
53 8
168
33.3
115
79.5
■229
—
—
104
500
208/230-3-60
187
253
399.4
450
722
89 7
446
67 9
345
89.7
446
89 7
446
600
460-3-60
414
506
196.3
225
361
43.6
223
34 6
173
43 6
223
43 6
223
100
575-3-60
518
633
168.0
200
286
36.5
164
28.8
120
36 5
164
36 5
164
200
380-3-60
342
418
205 9
250
396
45.5
247
34 6
191
45 5
247
45.5
247
900
380/415-3-50
342
440
196.7
225
363
43.6
223
34 6
173
43.6
223
43.6
223
300 (PW)
346-3-50
325
380
205 6
250
298
44 9
148
33 3
229
44 9
148
49 9
148
LEGEND
—
— Not Applicable
FLA
— Full Load Amps
ICF
— Maximum Instantaneous Current Flow During Starting (The
point in the starting sequence where the sum of the LRA
for the starting compressors, plus the total RLAforall run
ning compressors, plus the FLA for all running fan mo
tors is maximum)
kcmil
— Thousand Circular Mils
LRA
— Locked Rotor Amps
MCA
— Minimum CircuitAmps (used for sizing, complies with Na
tional Electrical Code [NEC] [ U S A Standard],
section 430-24).
MOCP
— Maximum Overcurrent Protection (used for sizing
disconnect, compiies with NEC [U.S A Standard],
section 440-22)
RLA
— Rated Load Amps
‘Units are suitable for use on electrical systems where voltage sup
plied to unit terminals is within listed minimum to maximum limits
tAII compressors are across-the-line start only except 346-V, 3-ph,
50-Hz units.
NOTES.
1 Maximum allowable phase imbalance: voltage - 2%; amps -10%
2. Maximum incoming wire size for terminal block is 500 kcmil
3. For units 38AFI094 and 104 compressor model numbers, see table
below
UNIT 38AH
094
104
CKT
A1
A2
B1
A1
A2
B1
B2
MODEL
NO. 06E
-275
-250
-299
-265
-250
-265
-265
25