Table 6A — Refrigerant Piping Requirements — 38AH044-104 Dual-Circuit Units — 60 Hz
TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE — FT (M)
UNIT 38AH
15-25
25-50
50-75
75-100
100-150
150-200
(4.6-7.6)
(7.6-15.2)
(15.2-22.9)
(22.9-30.5)
(30.5-45.7)
(45.7-61.0)
L
s
L
S
L
S
L
S
L
S
L
s
044
Ckt A
%
1%
У8
1У8
Ув
2Ув
Уе
2Уе
Уе
2Ув
Va
2Ув
Ckt В
%
1%
У8
1%
Ув
2Ув
Ув
2Ув
Va
2Уе
Va
2Ув
054
Ckt A
%
1%
У8
1%
Ув
2Ув
Va
2Ув
Va
2Ув
Va
2Ув
Ckt В
У8
1%
У8
2У8
Ув
2Ув
1Ув
2Ув
1Ув
2Ув
1У8
2%*
064
Ckt A
%
1%
У8
2Ув
Ув
2Ув
Уе
2Ув
1Уе
2Ув
1Ув
2%t
Ckt В
%
2Ve
У8
2Ув
Ув
2Ув
1Ув
2Ув
1У8
2%
1У8
2%
074
Ckt A
%
2Ve
У8
2Уа
Ув
2Ув
1Ув
2Ув
1Ув
2%t
1У8
2%t
Ckt В
%
2V8
1У8
2У8
1У8
2Ув
1Ув
2%
1Ув
2%
1%
2%
084
Ckt A
%
2V8
1Ув
2Ув
1Уе
2Ув
1У8
2%t
1%
2%t
1Ув
2%t
Ckt В
V8
2Уа
1У8
2Ув
1Ув
2Ув
1Ув
2%
1У8
2%
1Ув
2%
094
Ckt A
%
2V8
1Уб
2Уа
1
Ve
2%t
1Ув
2%t
1%
2%t
1%
ЗУв“
Ckt В
%
2Ve
Ув
2У8
V/a
2Ув
1Ув
2%
1Уа
2%
1Ув
2%
104
Ckt A
%
2Ув
1У8
2Ув
1Ув
2%t
1Уз
2%t
1Ув
2%t
1У8
ЗУв“
Ckt В
%
2Ув
1Уб
2Ув
1Ув
2Уе
1Ув
2%
1%
ЗУв“
1У8
ЗУв“
LEGEND
CV
— Constant Volume
L
— Liquid Line
S
— Suction Line
VAV
— Variable Air Voiume
‘Double suction riser required on units with field installed unloader
on circuit В compressor if condensing unit is elevated above
evaporator.
tDouble suction riser required on units with field installed unloader
on circuit В compressor if condensing unit is elevated above
evaporator.
“Double suction riser required on all unit configurations if condens
ing unit is elevated above evaporator.
NOTES:
1.
Addition
of
2
unloaders
to
circuit
В
compressor
is
not
recommended
2
38AH094 and 38AH104 piping sizes apply only to factory sup
plied unit configurations They do NOT take into account any field
installed unloaders
3
Piping sizes are based on unit operation above 40 F (4 4 C) satu
rated suction temperature (SST) When operating below 40 F
(4 4 C), refer to Carrier System Design Manuai, E20-IÌ piping de
sign program, or ASHRAE Handbook to select proper line sizes
4
Pipe sizes are based on the total linear length shown for each
column, plus a 50% allowance for fittings.
5
Suction and liquid line sizing is based on pressure drop equivalent
to 2 F (1.1 C) at nominal rating conditions. Higher pressure drop
design criteria may allow selection of smaller pipe sizes, but at a
penalty of decreased system capacity and efficiency
6.
Double suction risers may be required if condensing unit is el
evated above the evaporator See footnotes and double suction
riser table below
7 Refer to Carrier System Design Manual or to E20-II design
programs for further information on selecting pipe sizes for split
systems
8. All pipe sizes are OD inches Equivalent sizes in millimeters
follow
in.
mm
%
15.9
Уе
22.2
v/a
28.6
V/a
34 9
V/a
41 3
2Уа
54 0
2%
66 7
ЗУв
79 4
3%
92 1
Table 6B — Refrigerant Piping Requirements for Double Suction Risers,
38AH054-104 Duai-Circuit Units — 60 Hz
TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE — FT (M)
UNIT 38АН
50-75
75-100
100-150
150-200
15.2-22.9)
(22.9-30.5
30.5-45.7
(45.7-61.0
A
В
С
А
В
С
А
В
С
А
В
С
054
Ckt А
Ckt В
_
—
—
—
—
—
___
___
—
V/a
2Ув
2%
064
Ckt A
Ckt В
_
___
—
—
—
—
___
—
___
V/a
2Va
2%
074
Ckt A
Ckt В
_
___
—
—
___
—
1Ув
2Ув
2%
1Ув
2Уа
2%
084
Ckt A
Ckt В
_
—
—
1Ув
2Уе
2%
1Уе
2Ув
2%
V/a
2Va
2%
094
Ckt A
Ckt В
1У8
2Ув
2%
V/a
2Ув
2%
1%
2Ув
2%
V/a
2%
ЗУв
104
Ckt A
1Ув
2Ув
2¥а
V/a
2Ув
2%
1Ув
2Ув
2%
V/a
2%
ЗУв
Ckt В
—
—
—
—
—
—
1Ув
2%
ЗУв
V/a
2%
ЗУв
LEGEND
—
— Not Required
Pipe A
— Suction Riser Without Trap
Pipe B
— Suction Riser With Trap
Pipe C
— Suction Line to Condensing Unit
NOTES.
1 See Refrigerant Piping Requirements table at top of page to de
termine need for double suction risers.
2 Pipe sizes are based on the total linear length, shown for each
column, plus a 50% allowance for fittings.
Suction and liquid line sizing is based on pressure drop equivalent
to 2 F (1 1C) at nominal rating conditions Higher design pressure
drop criteria may allow selection of smaller pipe sizes but at a pen
alty of decreased system capacity and efficiency.
Refer to Carrier System Design Manual or to E20-II design
programs for further information on selecting pipe sizes for split
systems
All pipe sizes are OD inches. See Table 6A notes for metric
equivalents
Refer to Fig. 13 for double suction riser construction
16