A caution, Adjust refrigerant charge – Carrier 38AH044-134 User Manual
Page 39
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Preriminary Charge — Refer to GTAC n (General Train
ing Air Conditioning), Module 5, Charging, Recovery, Re
cycling, and Reclamation for charging procedures. Using the
liquid charging method and charging by weight proced^ure,
charge each circuit with the amount of R-22 listed in Table
3A, 3B, 4A, or 4B.
A
CAUTION
Never charge liquid into the low-pressure side of sys
tem. Do not overcharge. During charging or removal of
refrigerant, be sure indoor-fan system is operating.
Start Unit — The field disconnect is closed, the fan cir
cuit breaker is closed, and the space thermostats are set above
ambient so that there is no demand for cooling. Only the
crankcase heaters are energized.
Close the compressor circuit breakers and then reset both
space thermostats below ambient so that a call for stage one
cooling is ensured. Lead refrigeration circuit ther
mostat TCI must be set to call for cooling at a lower tem
perature than lag refrigeration circuit thermostat TC2.
See Table 15 for lead/lag circuits on all units. Now set TC2
for cooling.
NOTE: Do not use circuit breakers to start and stop the com
pressor except in an emergency.
38AH044-084 DUAL-CIRCUIT UNITS — Start-up of lead
compressor A1 (Table 16) will be delayed from 12 seconds
to 5Vi minutes from the time the call for cooling is initiated
by TCI. After the lead compressor starts, close the TC2 ther
mostat to start lag circuit compressor Bl. Compressor B1
will start a minimum of 60 seconds after thermostat TC2 is
closed.
38AH044-084 OPTIONAL SINGLE CIRCUIT UNITS —
Start-up of lead compressor A1 (Table 16) is delayed from
12 seconds to 5V2 minutes from the time the call for cooling
is initiated by TCI. Closure of TC2 will actuate LLS-A2.
Lag compressor A2 is controlled by D-D2 timer contacts and
capacity control pressure switches (CCPSs) which monitor
compressor suction pressure. The lag compressor starts ap
proximately
2
V
2
minutes after the lead compressor starts if
the suction pressure is above the CCPS set point.
38AH094,104 UNITS — Start-up of lead circuit A,
compressor A1 (Table 16) is delayed from 12 seconds to
5
V
2
minutes from the time the call for cooling is initiated.
After lead circuit A, compressor A1 starts, close refrigera
tion circuit thermostat TC2 to start lag circuit B, lead com
pressor BL Start-up of compressor Bl is delayed from
12 seconds to 5
'/2
minutes. (Circuit B of unit 38AH094 has
only one compressor.)
Each circuit’s lead compressor start-up is controlled by
the unit control timer. The circuit’s lag compressor start-up
is controlled by the D-D2 timer contacts and capacity
control pressure switches (CCPSs) which monitor compres
sor suction pressure. The circuit’s lag compressor will start
approximately 2
*/2
minutes after a call for cooling if com
pressor pressure is above CCPS set point.
38AH124,134 UNITS — Start-up of the lead circuit
(Module 124A or 134A) lead compressor A1 (Table 16) is
delayed from 12 seconds to
5
V
2
minutes from the time the
call for cooling is initiated by TCI. Lag compressor A2 is
controlled by D-D2 timer contacts and capacity control pres
sure switches (CCPSs) which monitor compressor suction
pressure. The lag compressor starts approximately
2
V
2
min
utes after the lead compressor starts if the suction pressure
is above the CCPS set point.
After the lead circuit (Module 124A or 134A) lead com
pressor A1 (Table 16) starts, close the TC2 thermostat to start
the lag circuit (Module 124B or 134B) lead compressor (Al).
Lag circuit compressor Al start-up is delayed from 12 sec
onds to
5
V
2
minutes from the time the call for cooling is
initiated by TC2. Lag compressor A2 is controlled by D-D2
timer contacts and CCPSs which monitor compressor suc
tion pressure. Lag compressor A2 starts approximately 2Vi
minutes after lead compressor Al starts if the suction pres
sure is above the CCPS set point.
Adjust Refrigerant Charge
A
CAUTION
Never charge liquid into the low-pressure side of sys
tem. Do not overcharge. During charging or removal of
refrigerant, be sure indoor-fan system is operating.
With all fans operating, and all compressors on the cir
cuit being serviced operating at full capacity, adjust the re
frigerant charge in accordance with the unit charging charts
located on the inside of the control box doors and in Fig.
30-43. Charge vapor into compressor low-side service port
located above oil pump crankshaft housing. Measure pres
sure at the liquid line service valve, making sure a Schrader
depressor is used if required. Also, measure liquid line tem
perature as close to the liquid service valve as possible. Add
charge until the pressure and temperature conditions of the
charging chart curve are met. If liquid pressure and tempera
ture point fall above curve, add charge. If liquid pressure
and temperature point fall below curve, reduce the charge
until the conditions match the curve.
If the sight glass at location A (Fig. 11 and 12) is cloudy,
check refrigerant charge again. Ensure all fans and com
pressors on the circuit being serviced are operating. Also
ensure maximum allowable liquid lift has not been
exceeded.
If the sight glass at location A is clear and the sight glass
at location B is cloudy, a restriction exists in the line be
tween the 2 sight glasses. Check for a plugged filter drier or
partially open solenoid valve. Replace or repair, as needed.
Table 16 — Index of Lead/Lag Circuits and Compressors
UNIT 38AH
044-084
STD
044-084
OPT
094
104
124
134
LEAD CIRCUIT
A
A
A
A
Module
124A
Module
134A
Compressor, Lead
Compressor; Lag
AJ
At
A2
At
A2
At
A2
Al
A2
Al
A2
LAG CIRCUIT
В
t
В
В
Module
124B
Module
134B
Compressor, Lead
Compressor; Lag
Bl
*
Bl
*
Bl
B2
Al
A2
Al
A2
4
^
LEGEND
OPT
— Optional Single-Circuit Units
STD
— Standard Dual-Circuit Units
‘Circuit has only one compressor
fUnits have only one circuit
39