Step 5 — install accessories, Pre-start-up, System check – Carrier 38AH044-134 User Manual
Page 37: A caution, Start-up
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Table 15 — Main Power Connection and Control Circuit Wiring
MAIN POWER CONNECTION
CONTROL CIRCUIT
Electrical
Characteristics
(V-Ph-Hz)
Qty
Terminal
Blocks
Qty
Parallel
Conductors*
Max Wire
Size
(kcmil)
Control Power
(V)
Safety Circuit
(V)
208/230-3-60
1
6
500
115f
24
460-3-60
575-3-60
1
3
500
115t
24
230-3-50
1
6
500
230
24
380-3-60
380/415-3-50
1
3
500
230
24
346-3-50
1
3
500
200
24
LEGEND
kcmil —
Thousand Circular Mils
‘Conductors are from the safety disconnect.
tControl power is accomplished with a step-down transformer where primary voltage is field voltage
Step 5 — Install Accessories
LOW-AMBIENT OPERATION
Units 38AH044-084. 124, and 134 — If operating tempera
tures below 55 E (13 C) are expected, Motormaster® III fan
motor control is recommended. Refer to separate installa
tion instructions for low-ambient operation guidelines.
Units 38AH094 and 104 — If operating temperatures below
45 F (7 C) are expected, Motormaster III fan motor control
is recommended. Refer to separate installation instructions
for low-ambient operation guidelines.
MISCELLANEOUS ACCESSORIES — For applications re
quiring special accessories, the following packages are avail
able; condenser coil hail guard package, gage panel, unloader
package, unloader conversion kits, sound reduction pack
age, condenser coil protective grilles, compressor security
grilles, ModuPaneFM control, and thermostat transformer re
lay package.
PRE-START-UP
IMPORTANT: Before beginning Pre-Start-Up or Start-
Up, review Start-Up Checklist at the back of this pub
lication. The Checklist assures proper start-up of a unit
and provides a record of unit condition, application re
quirements, system information, and operation at ini
tial start-up.
Do not attempt to start the air-conditioning system until
following checks have been completed.
System Check
1. Check all system components, including the air
handling equipment. Consult manufacturer’s instruc
tions. If the unit has field-installed accessories, be sure
all are properly installed and wired correctly. Refer to
unit wiring diagrams.
2. Backseat (open) compressor suction and discharge shut
off valves. Close valves one turn to allow refrigerant pres
sure to reach the test gages.
3. Open liquid line service valves.
4. Check tightness of all electrical connections.
5. Oil should be visible in the compressor sight glasses.
See Fig. 29. An acceptable oil level in the compressor
is from Vs to Vs of sight glass. Adjust the oil level as
required. No oil should be removed unless the crank
case heater has been energized for at least 24 hours. See
Start-Up section on page 38, Preliminary Oil Charge,
for Carrier-approved oils.
6. Electrical power source must agree with unit
nameplate.
A
CAUTION
Crankcase heaters on all units are wired into the control
circuit, so they are always operable as long as the main
power supply disconnect is on (closed), even if any safety
device is open. Compressor heaters must be on for 24
hours prior to the start-up of any compressor.
7. Crankcase heaters must be firmly locked into compres
sors, and must be on for 24 hours prior to start-up.
8. Fan motors are 3-phase. Check rotation of fans during
first start-np check. Fan rotation is clockwise as viewed
from top of unit. If fan is not turning clockwise, reverse
2 of the power wires.
9. Check compressor suspension. On units 38AH044-084,
124, and 134, snubber washers (for noise suppression)
can be moved with finger pressure. On units 38AH094
and 104, rails allow compressors to float freely on com
pressor rail springs.
10. On 38AH074,084 single-circuit units and Modnle
38AH134B, ensure that the packaging block located be
tween the oil eqnalization tube and the compressor cross
brace has been removed.
START-UP
Compressor crankcase heaters must be on for 24 hours
before start-up. To energize the crankcase heaters, set the
space thermostat above the ambient so there will be no de
mand for cooling. Close the field disconnect and turn on the
fan circuit breakers. Leave the compressor circuit breakers
off/open. The crankcase heaters are now energized.
37