beautypg.com

Carrier 38AH044-134 User Manual

Page 47

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Fig. 45 — Accumulator and Fusible Plug

Timer Functions — (See Timer Cycle, Fig. 47.) Each
refrigeration circuit is controlled by an independent timer

which allows for the independent operation of each refrig­
eration circuit.

NOTE: Unit 38AH044-084 optional single-circuit units have

one timer which controls the lead compressor. Lag compres­
sor is controlled by CCPS (capacity control pressure switch).

SWITCH A — The timer is energized through contacts A-Al
or A-A2. This establishes the Time Guard® function which
prevents compressor short-cycling. Start of compressor is de-

i

layed approximately 5.5 minutes after shutdown.

^' SWITCH B — The compressor is initially energized through

contacts B-Bl.

SWITCH D — Contacts D-Dl provide a 2*/2-minute bypass
of the low-pressure switch at start-up for winter-start con­
trol. On 38AH044-084 optional single-circuit units, contacts

D-D2 control start-up of compressor A2.

SWITCH E — Contacts E-EI provide a 40-second bypass
of the oil pressure switch at start-up. If oil pressure does not

build to the required minimum pressure in 40 seconds, the

compressor shuts down and the control circuit locks out.

On 38AH044-084 dual-circuit and 38AH094,104 units, lag

circuit B start-up is delayed 60 seconds after a call for cool­
ing is made to the circuit. This prevents compressor(s) in
both lead and lag circuits from starting at the same time.

Control Circuit Reset — The control circuit locks out
if the unit shuts down because of low oil pressure, high dis­
charge gas temperature (DGT), or excessive high-side pres­
sure. To reset the control circuit, open and close the fan cir­
cuit breaker (FCB). This resets the timer, and the unit restarts
under Time Guard control. At start-up, if the low-pressure

switch (EPS) does not close after 2'/2 minutes, the unit shuts

down. When the pressure builds enough for the EPS to cut
in, the control circuit is energized automatically and start-up
proceeds under Time Guard control.

TO PREVENT REFRIGERANT LEAKAGE)

Fig. 46 — Pressure-Actuated Capacity Control Valve

CONTROL

Sequence of Operation — Units are controlled with

electromechanical components. Each refrigeration circuit

(except 38AH044-084 optional single-circuit units) is oper­

ated by an independent timer which controls the operation

sequence of each circuit.

On a call for cooling, first stage cooling thermostat TCI

closes. Condenser fans and timer (TM) are energized. After

approximately 7 seconds, timer contacts E-El close. Ap­
proximately 12 seconds after TCI closes, normally-open timer
contacts B-B1 close for 1 second. This energizes compres­

sor A1 contacts CAl and starts the compressor. At the same

time, solenoid drop relays (SDRs) and liquid line solenoid
valve no. 1 (EES-A for 38AH044-084 dual-circuit units;
EES-Al for all other units) open, and timer relay no. 1 (TR2)

is energized. Normally open TR2 contacts close, completing
a circuit around B-Bl and through compressor A1 contac­
tors to maintain compressor operation when B-Bl contacts
open. Contacts E-El remain closed for approximately 40 sec­
onds to bypass the oil pressure switch (OPS). If oil pressure
is insufScient when contacts E-El open, the compressor stops,
the timer cycles off, and the control circuit locks out. At start­
up, timer contacts D-Dl are closed, bypassing low-pressure
relay contacts EPR-A for 21/2 minutes. This provides a win­

ter start-up feature.

Approximately 2V2 minutes after TCI closes, timer con­

tacts D-Dl open and D-D2 close. If pressure is insufficient
to close the low-pressure switch, the low-pressure switch re­

lay is open, the compressor shuts down, and the Time Guard
control is initiated. (Time Guard control prevents compres­
sor from restarting for 5 minutes after the demand for cool­
ing is satisfied.)

47