beautypg.com

0 maintenance/ service procedures (cont'd), 9 other controls, 8 optional dampers and damper controls – Reznor MAPS - A,B,C Users Manual User Manual

Page 20

background image

Form O-MAPSIII&IV Cabinets A/B/C, Page 20

Refer to Control

Instruction Form

CP-MAPS D15/16/17/18

for information on the

programmable controller.

I/Q System

Controller

BACview

Display

All MAPS

®

systems have a unit-mounted,

24-volt I/Q programmable controller.

Depending on how it was ordered, the

system is equipped for either neutral air/

discharge air control (Option D15) or

space control with discharge air reset

(Option D16). In addition, MAPS

®

IV elec-

tric heat Model RECC for process appli-

cations may have neutral air/discharge

air control (Option D17) or space control

with discharge air reset (Option D18). The

controller is factory programmed to match

the selection. See the control instruction

manual, Form CP-MAPS D15/16/17/18, for

more details.

FIGURE 8 - I/Q

System Program-

mable Controller

and Unit Module

Interface with Display

3.9.3 Motor Starter

(Option AN10) or

Variable Frequency

Drive (Option VFD2)

Function: When the main controller calls for blower operation, either an IEC type

starter with a contactor or a variable frequency drive (VFD) module responds to oper-

ate the motor.
The starter is in the high voltage control compartment. The VFD was field installed in

a location that is no more than 50 feet (15M) away where the minimum temperature

is 18°F (-9°C). Control of the variable frequency drive module is coordinated with the

main controller, and depending on what was ordered, can function in response to tem-

perature, CO2, or pressure controls.
Service: If a starter or contactor need replaced, use only the identical replacements

that are designed to match the motor and voltage of the system.

3.9.2 Air Proving

Switch

Function: The airflow proving switch is a pressure switch that verifies

to the main controller that the blower is operating.
Service: If the switch needs to be replaced, use a factory-authorized

replacement designed for the application.

3.9 Other Controls

3.9.1 Programmable Digital Controller and Sensors

3.8 Optional Dampers and Damper Controls

Inlet Air Dampers

Location: Dampers and damper motors are located in the inlet air opening.

Function: Dampers operate in response to a variety of controls (GF Options).

Service: Clean dampers and controls of dust and dirt.

2-Position Damper Motor (Options AR8, AR2D, AR2L)

Function: The 2-position damper motor opens and closes the dampers in response to

unit operation or a field-supplied time clock. The motor closes the dampers on heater

shutdown.

Modulating Motor (Options AR25, AR2G, AR2H, AR2K)

Function: The modulating damper motor actuates the dampers in response to the

selected control with actuation from input switch settings.

The motor closes the inlet dampers on heater shutdown.
Service: Other than external cleaning, there is no service required on the dampers or

the damper motor. If the damper, control, or motor need to be replaced, replace with a

factory-authorized replacement.

For additional information on damper controls (Options GF 1-9), see the system instal-

lation manual Form I-MAPSIII&IV.

FIGURE 7 - Damper

Motor

3.0 Maintenance/

Service

Procedures

(cont'd)

Some sensors are standard and others will depend on option selection.
Service: If a sensor needs to be replaced, use only a factory authorized replacement

part designed for the purpose. Refer to the digital wiring requirements in Paragraph 7.4

of Installation Form I-MAPSIII&IV.
If a controller needs to be replaced, it must be replaced with the same controller and

software.