beautypg.com

0 maintenance/ service procedures (cont'd), 6 compressor maintenance (cont'd) – Reznor MAPS - A,B,C Users Manual User Manual

Page 18

background image

Form O-MAPSIII&IV Cabinets A/B/C, Page 18

Record the ambient temperature. Adjust the system controller so that a call for

cooling exists.
NOTE: Outdoor ambient lockouts may prevent mechanical cooling. Temporarily

override lockouts by lowering the cooling setpoint. When testing is complete, reset

the controller.
Because it is possible to unknowingly connect 3-phase power in such a way

as to cause the scroll compressor or blower to rotate in reverse, it is very

important to check this on startup.

Check Compressors - Immediately at startup, observe the gauges. If the

suction pressure rises and discharge pressure drops, the compressor is

operating in reverse and must be shut down. Turn off the power and switch

the 3-phase line voltage wiring connections before restarting the unit.

Important: If allowed to operate for several minutes in reverse, the compressor’s

internal protector will trip. If a compressor is repeatedly allowed to restart and run

in reverse, the compressor will be permanently damaged.

Step 11. Check Subcooling and Superheat

Superheat is the verification that the evaporator coil is properly using the

refrigerant supplied. Too much superheat indicates that the coil is undercharged.

Too little superheat indicates that the coil is overcharged and potentially flooding

liquid refrigerant to the compressor.
Subcooling is the measurement of liquid refrigerant stored in the condenser

coil. Too much subcooling indicates a system overcharge. Too little subcooling

indicates a system undercharge and may not provide the thermal expansion valve

with a full column of liquid refrigerant for proper operation.
Two important requirements before checking superheat and subcooling:
1) This unit has fully intertwined refrigerant circuits and each circuit MUST be

isolated before measuring its temperature. Another active circuit will influence the

reading and make it impossible to determine accurate superheat and subcooling.
2) If the circuit is equipped with an optional hot gas bypass valve, the valve must

be disabled before measuring superheat and subcooling. Method of disabling

depends on the model and date of manufacture.

All MAPS

®

IV Models & any MAPS

®

III Models with a shutoff valve in the line

between the compressor discharge and the hot gas bypass valve - Locate the

shutoff valve. Disable the hot gas bypass valve by closing the shutoff valve. When

measurements are complete, be sure to open the valve.

MAPS

®

III Models without a shutoff valve in the line between the compressor

discharge and the hot gas bypass valve - Disable the hot gas bypass valve by

removing the cover and adjusting the spring tension counterclockwise until the

spring tension is relieved.

Count and record the number of turns required so

that you can return the bypass valve to its original setting. To check setting, refer

to Paragraph 3.9.5.

3.6 Compressor

Maintenance

(cont'd)

Step 10. System

Startup (cont'd)

3.0 Maintenance/

Service

Procedures

(cont'd)

I

MPORTANT: Do not

release refrigerant

to the atmosphere!

If required service

procedures

include the adding

or removing of

refrigerant, the

qualified HVAC

service technician

must comply with

all federal, state or

provincial, and local

laws.

Follow the procedures in Paragraph 3.5 to check subcooling and superheat.

Step 12. (Select the procedure that applies.)

IF the oil measured in Step 2 was significantly less than in the table on

page 14 or the acid test in

Step 2 indicated a burnout, do the following:

a) Operate the unit for several hours. Check the pressure drop through the

temporary suction line filter drier. If the pressure drop exceeds 8 psig, recover

the refrigerant, replace the suction line filter drier with the same type as

removed, replace the liquid line filter drier, evacuate the circuit, and re-charge

with the recovered refrigerant.

Continue to monitor the pressure drop through the suction line filter drier and

repeat the process above until the pressure does not exceed 8 psig after

several hours of operation. (

NOTE: System must be allowed to run no more

than 72 hours with a suction line filter drier.)

b) Allow the system to operate for 4-8 hours. Recover the refrigerant and take an

oil sample. Retest the oil for acid.

NOTE: To identify MAPS

®

III

and MAPS

®

IV Models, see

Paragraph 1.0.