beautypg.com

Reznor MAPS III, Cabinet D RECB Users Manual User Manual

Page 42

background image

Form O-MAPSIII Cabinet D, P/N 222918R9, Page 42

Gas Heat Section Modulating Control LOCKOUT ERRORS (ccont'd)

Code

Alert

Description

Probable Causes

Solutions

Gas Sensor

Failure (EO6)
Pressure

Sensor

Reading Low

The gas transducer reading

is too low compared to

the expected value for the

modulating gas valve actuator

position.
When the furnace is operating

at 75% or higher -- greater

than 8 VDC analog input

voltage - the manifold

pressure sensor must read

1.4" w.c. or higher

A. Modulating actuator/ball

valve not properly aligned

1 Perform modulating system gas valve alignment

procedure; see Paragraph 4.3.

B. Line pressure too low

1. Ensure line pressure is properly adjusted for the gas and

application. Correct as needed.

C. Intermediate regulated

pressure to low

1. Ensure the safety gas valve(s) are properly adjusted

to the specified outlet pressure. Adjust per the installation

instructions as necessary.

D. Wrong gas pressure

sensor installed.

1. Ensure the proper gas transducer - either natural gas or

propane - is installed. Replace as needed.

E. Gas pressure sensor

faulty

1. Ensure gas manifold transducer is installed properly and

wired per the unit wiring diagram. Replace as necessary.

Gas Sensor

Failure (EO7)
Pressure

Sensor

Reading High

The gas transducer reading

is too high compared to

the expected value for the

modulating gas valve actuator

position.
When the furnace is operating

at 75% or lower - less than 8

VDC analog input voltage --

the manifold pressure sensor

must read 2.8" w.c. or lower.

A. Modulating actuator / ball

valve not properly aligned

1. Perform modulating system gas valve alignment

procedure; see Paragraph 4.3.

B. Line pressure too high

1. Ensure the line pressure is properly adjusted for the gas

and application. Correct as necessary.

C. Intermediate regulated

pressure too high

1. Ensure the safety gas valve(s) are properly adjusted

to the specified outlet pressure. Adjust per the installation

instructions as necessary.

D. Wrong gas pressure

sensor installed

1. Ensure gas sensor -- either natural or propane -- is

installed. Replace as necessary.

E. Gas pressure sensor

faulty

1. Ensure gas sensor is installed properly and wired per the

unit wiring diagram. Replace as necessary.

Improper Flame

Signal (EO8)

Control senses flame present

when the gas valve is

commanded off.

A. Flame remains lit in “Off”

cycle

1. Gas valve leaks - check wiring to remove continuous 24V

to gas valve.
2. Gas valve is stuck open – remove, repair, or replace gas

valve.

No Firing Rate

Input (EO9)

Call for heat is sensed (R & W

closed) but firing rate is below

defined voltage threshold for

furnace operation.

A. Faulty wiring into the

“Analog +” and “Analog –“

terminals

1. Ensure wiring is connected per unit wiring diagram.
2. Check for loose pins or bad connections.

3. Check for frayed wiring or shorts to ground.

B. No signal from source.

1. Check firing rate input voltage – must be greater than 1.5

VDC.
2. Troubleshoot controller providing firing rate input to the

deep modulation ignition control board.

Invalid I.D. Plug

(Eid)

The installed I.D. plug is not

valid for this control board.

A. Incorrect I.D. plug installed 1. Ensure I.D. plug is correct for the furnace – check label.

2. Ensure I.D. plug is properly inserted into the mating

connector on the control board.
3. With the I.D. plug installed, cycle power to the furnace.

The board will display the I.D. plug identity upon power-up.
4. Install correct I.D. plug as needed.

6.2 Troubleshooting Heat Section (cont'd)

6.2.2.2 Troubleshooting the Modulating Gas Control (cont'd)