beautypg.com

Reznor MAPS III, Cabinet D RECB Users Manual User Manual

Page 25

background image

Form O-MAPSIII Cabinet D, P/N 222918R9, Page 25

Instructions to Re-Assemble the Gas Heat Section (Refer back to

FIGURES 7, 8, and 9.)

1. Re-attach the Heat Exchanger Panel - Re-attach the access panel being sure to

use all of the screws. See

FIGURE 7. Reconnect the limit switch wire.

2. Re-attach the venter assembly using all of the screws removed. See FIGURE 8.

Re-connect the venter wires at the board. If installing a replacement motor, check

the wiring diagram for connections.

3.

Re-install the Burner and Manifold

a) Slide the entire venturi/burner assembly into position.

b) Re-connect the ignitor and sensor wires. Verify that the wires and the

connections are good

c) Insert all of the screws along the top and the bottom. Re-attach the burner end

shield.

d) Re-connect the gas train. Be careful not to rotate the section attached to

the venturi/burner. Check the burner orifice to be sure that it is secure and

positioned properly.

4. Check the wiring and sensing tube connections. Turn on the electric and the

gas. Leak test the connections with a leak detecting solution. Check for proper

operation.

4.1.4 Re-Assemble

the Heat Exchanger

Panel, Burner, Gas

Train, and Venter

4.2.1 General

FIGURE 12 - Gas Heat

Section Controls in a

MAPSIII "D" Cabinet

The heat section controls

are located on the floor

of the heat section; .see

FIGURE 1, page 4.)

Terminal Blocks

Pressure Switch

(Combustion Air)

Transformer

75VA

Ignition Board (See FIGURE 14.)

Gas Heat Section

Electrical Box -

Applies to All Sizes

(furnace with modulating burner)

Gas Heat Section Electrical Box -

Applies only to Sizes 1000, 1200,

1400, 1600 with two furnace

sections

(Non-modulating heat section

is closest to the blower.)

Terminal

Blocks

Pressure

Switch

(Airflow)

Pressure Switch

(Combustion Air)

PAM

Relay

Venter Motor Capacitor Bracket

Transformer 30VA

Transformer

75VA

Modulating Ignition

Board with ID Plug

(See FIGURE 13A.)

Fuse

Holder

Thermal Circuit

Breaker

NOTE: Configuration of

heat sections in relation to

the blower depends on date

of manufacture. Currently

manufactured systems with

two heat sections have the

non-modulating furnace

closest to the blower and

the modulating furnace

downstream. Previously

manufactured systems

may have the opposite

configuration.

IMPORTANT NOTE: The information in Section 4.2 applies to standard natural gas

MAPSIII D Cabinet Models RDCB and RDDB manufactured beginning 12/2011. A

Model RDCB or RDDB manufactured prior to 12/2011 may also have these gas control

components. The identification of the ignition board in the Serial No. on the heat sec-

tion rating plate will determine whether this information applies. If the ignition code in

the serial number is 96, the information in Section 4.2 applies. If the ignition code is 90,

91, 92, or 93, contact your representative or distributor or search RezSpec.com for a

previous version of this manual.

Serial No. Sample: 3 BKH 789 BK 08 N 96 7D

Also, if the unit is propane ("N" in the Serial No. is an "L"), modulation control informa-

tion here does not apply. Refer to the rating plate or contact your distributor for infor-

mation.