beautypg.com

Reznor MAPS III, Cabinet D RECB Users Manual User Manual

Page 29

background image

Form O-MAPSIII Cabinet D, P/N 222918R9, Page 29

Ignition System

Fault Modes - Non-

Modulating Furnace

of D Cabinet with Size

1000, 1200, 1400, or

1600 Heat Section

If flame is not established on the 4th trial for ignition (initial try plus 3 re-tries), the circuit

board de-energizes the gas valve and goes into lockout. The circuit board goes to one

flash on the green LED to indicate ignition failure lockout.
Limit Switch Operation - The limit switch is ignored unless a call for heat is present

(W energized). If the limit switch is open and a call for heat is present, the control de-

energizes the gas valve and runs the blower motor on heat speed and runs the venter

motor. The control will be in soft lockout and flashing fault code "3" before returning to

normal operation.

When the switch re-closes or the call for heat is lost, the control runs the venter motor

through post purge and the blower through the selected fan off delay.
Pressure Switch - If the pressure switch opens before the trial for ignition period, the

venter motor will run through the pressure switch recognition delay (2 seconds), the

gas valve will be de-energized, and the venter motor will run through the postpurge

time. The ignition system circuit board will re-start the heat cycle at the pressure switch

proving state if the call for heat still exists.

Pressure switch opening for less than 2 seconds during the trial for ignition period shall

not interrupt the heat cycle. (Gas valve will de-energize while the pressure switch is

open.)

If the pressure switch opens after a successful ignition, the circuit board will de-ener-

gize the gas valve. If flame is lost before the end of the 2 second pressure switch rec-

ognition delay, the circuit board will respond to the loss of flame. If the pressure switch

remains open for 2 seconds and the flame remains, the circuit board de-energizes the

gas valve and the venter motor runs through postpurge
Undesired Flame - If flame is sensed longer than 20 seconds while the gas valve

is de-energized, the circuit board shall energize the venter motor. When flame is no

longer sensed, the venter motor will run through postpurge. The circuit board will do

a soft lockout, but will still respond to open limit and flame. The FLAME (yellow) LED

flashes rapidly.
Gas Valve Relay Fault - If the circuit board senses the gas valve as energized for

more than one second when the circuit board is not attempting to energize the gas

valve, or the gas valve is sensed as not energized when it is supposed to be energized,

then the circuit board will lockout with the green LED off. The control assumes either

the contacts of the relay driving the gas valve have welded shut, or the sensing circuit

has failed. The venter motor is forced off to open the pressure switch to stop gas flow

unless flame is present.

If the gas valve was sensed as closed when it should be open, and has not de-ener-

gized after the venter motor was shutoff for 15 seconds, then the venter motor is re-

energized to vent the unburned gas.
Soft Lockout - The circuit board shall not initiate a call for heat while in lockout. The

circuit board will still respond to an open limit and undesired flame. Lockout shall auto-

matically reset after one hour. Lockout may be manually reset by removing power from

the circuit board for more than one second or removing the call for heat for more than

one and less than 20 seconds.
Hard Lockout - If the circuit board detects a fault on the board, the status LED will

be de-energized, and the circuit board will lockout as long as the fault remains. A hard

lockout will automatically reset if the hardware fault clears.
Power Interruption - During a momentary power interruption or at voltage levels

below the minimum operating voltage (line voltage or low voltage) the ignition system

will self-recover without lockout when voltage returns to the operating range.
Power interruptions of less than 80mS shall not cause the circuit board to change

operating states. Power interruptions greater than 80mS may cause the circuit board

to interrupt the current operating cycle and re-start.