beautypg.com

3 gas train – Reznor MAPS III, Cabinet D RECB Users Manual User Manual

Page 30

background image

Form O-MAPSIII Cabinet D, P/N 222918R9, Page 30

Location: The gas train is visible with the heat section door open. See component

identification in

FIGURE 15.

Service: Carefully remove external dirt from the valves and check the wiring connec-

tions. Annually, in preparation for the heating season, check the dual, single-stage

operating valve to be sure that it shuts gas flow off completely.
If any gas valves or other gas train components need to be replaced, they must be

replaced with identical part or factory-authorized replacement.

Optional

Low Gas

Pressure

Switch

Manual

Shutoff Valve

(2nd furnace)

Dual, Single-Stage

Gas Valve (non-

modulating furnace)

Gas

Supply

Manual

Shutoff Valve

(1st furnace)

Ball Valve

with Actuator

(modulating

furnace)

Dual, Single-Stage Gas Valve

(modulating furnace)

Transducer

Optional High Gas

Pressure Switch

Pressure

Tap

Optional High Gas

Pressure Switch

FIGURE 15 - Gas

Train Components

NOTE: Heat section

Sizes 500, 600, 700, and

800 with one furnace

have manifold for

modulating furnace

only.

Dual Single-Stage Operating Gas Valve - All gas heat sections have one or two dual single-stage gas valves.

WARNING

he operating valve is the prime safety shutoff. All gas supply lines must be free of dirt or

scale before connecting to the unit to ensure positive closure. See Hazard Levels, page 2.

3) Use your finger to fully block the burner orifice. Continue blocking the orifice for

several seconds and observe the manometers. If any pressure is indicated, the

gas valve is leaking. A leaking gas valve must be replaced before the heater is put

back in operation.

4) Repeat the test with each dual single-stage gas valve.

FIGURE 17 - Ball

Valve and Actuator

in Modulating Gas

Control

The modulating furnace has a ball valve

with an actuator to control gas flow. The

ball valve and actuator are located down-

stream of the dual single-stage valve as

shown here.
Carefully clean external dirt accumula-

tion from the actuator.

1/8” Outlet

Pressure Tap

1/8” Outlet

Pressure Tap

FIGURE 16 - Top View of Dual Single-Stage

Gas Valve

The dual single-stage gas valve(s) must be checked

annually to ensure that each valve is shutting off gas flow

completely.

Instructions:

1) Locate the 1/8" NPT pressure taps on the

combination valve (see illustration on the left).

2) Turn the manual valve OFF to prevent flow to the

manifold. Connect a manometer to both of the 1/8”

outlet pressure taps.

NOTE: Manometers (fluid-

filled gauges) with inches water column scale are

recommended. Turn the manual valve ON and the

heater off.

4. Gas Heat

Section

Maintenance

(cont'd)

4.3 Gas Train