beautypg.com

0 troubleshooting (cont'd), Ignition module troubleshooting flow chart – Reznor MAPS III, Cabinet D RECB Users Manual User Manual

Page 38

background image

Form O-MAPSIII Cabinet D, P/N 222918R9, Page 38

Control Status - Green LED Codes

Steady ON ...... Normal Operation, No call for heat

Fast Flash ....... Normal Operation, Call for heat

1 Flash ............ System Lockout, Failed to detect or sustain flame

2 Flashes ........ Pressure Switch Did Not Close within 30 Seconds of Venter Motor

3 Flashes ........ High Limit or Flame Rollout Switch Open

4 Flashes ........ Pressure Switch is Closed Before Venter Motor is Energized

Steady OFF .... Blown fuse, No Power, or Defective Board

Flame Status - Yellow LED Codes

Steady ON ...... Flame is sensed

Slow Flash ...... Weak flame (current below 1.0 microamps ± 50%)

Fast Flash ....... Undesired Flame (valve open and no call for heat)

Operating and

Troubleshooting

Indicator Lights

on Control Module

used on the non-

modulating furnace

on Sizes 1000, 1200,

1400, and 1600

6.2 Troubleshooting Heat Section (cont'd)

Trial for Ignition

Call for Heat

Is there a

spark across gap at

ignitor?

Does gas

ignite?

Is there

minimum flame

current at the flame

sensor?

Is there

minimum flame

current at the control

module?

Replace control

module.

Check connections to

flame sensor or

moisture in bulkhead

connector.

Is the

flame sensor

corroded?

Clean flame

sensor.

Is the sensor

located in flame

correctly?

Replace flame

sesnsor.

Repositon

flame sensor.

Is gas

flowing?

Is the ignitor

position correct in the

gas flow?

Check gas pressure

and supply voltage. If

either are low, correct

and repeat startup.

Reposition

spark ignitor.

Is there

24VAC at the gas

valve?

Is there

24VAC from gas

valve output on control

module

to chassis?

Check wiring and

connections to

gas valve.

Replace

ignition

control

module.

Replace

gas valve.

Is there

spark voltage at

control?

Check high

voltage wire

continuity.

Is there

24V P1-2 to power

control?

Replace

control

module.

Check wiring

and/or 24VAC

transformer output.

YES

NO

YES

NO

YES

NO

YES

NO

YES

NO

YES

NO

YES

NO

YES

NO

NO

YES

YES

NO

YES

NO

YES

NO

Ignition Module

Troubleshooting

Flow Chart

Do not attempt to repair the DSI integrated control module (circuit board); the only field replaceable component is the

fuse.

IMPORTANT: When using a multimeter to troubleshoot the 24 volt circuit, place the meter’s test leads into the 5 or

9 pin connectors located on the ignition control. Do not remove connectors or terminals from the electrical components.

Doing so can result in misinterpreted readings due to the ignition control board’s fault mode monitoring circuits.

6.2.2.2

Troubleshooting

the Heat Section

Control Module (deep

modulation board)

used with Modulating

Gas Control

The control module

(P/N 257246) that operates the furnace in a MAPSIII Cabinet D

system has a built-in, self-diagnostic capability. The control continuously monitors its

own operation and the operation of the system. The LED on the control indicates the

current state, warnings, failures, and test modes.
IMPORTANT NOTE: The troubleshooting information applies to the control board that

is standard on MAPSIII D Cabinet Models RDCB and RDDB manufactured beginning

8/2011. A Model RDCB or RDDB manufactured prior to 8/2011 may have this board.

The ignition board is identified as

"96" in the Serial No. on the heat section rating plate.

Serial No. Sample: 3 BKH 789 BK 08 N 96 7D

If the ignition code in the serial number is 96, the following troubleshooting information applies. If the ignition code is 90,

91, 92, or 93, contact your representative or distributor or search RezSpec.com for a previous version of this manual.

6.0 Troubleshooting

(cont'd)

6.2.2 General Troubleshooting - Gas Heat Section (cont'd)

6.2.2.1 Troubleshooting the non-modulating furnace (cont'd)