beautypg.com

6 compressor maintenance and replacement, 0 maintenance/service procedures (cont'd) – Reznor MAPS III, Cabinet D RECB Users Manual User Manual

Page 10

background image

Form O-MAPSIII Cabinet D, P/N 222918R9, Page 10

R-410A Refrigerant

R-410A Refrigerant

R-410A Refrigerant

R-410A Refrigerant

Pressure Temperature

Pressure Temperature

Pressure Temperature

Pressure Temperature

PSI

°F

°C

PSI

°F

°C

PSI

°F

°C

PSI

°F

°C

1.8

-55

-48.3

56.4

6

-14.4

93.5

28

-2.2

143.3

50

10.0

4.3

-50

-45.6

57.9

7

-13.9

95.5

29

-1.7

156.6

55

12.8

7.0

-45

-42.8

59.3

8

-13.3

97.5

30

-1.1

170.7

60

15.6

10.1

-40

-40.0

60.8

9

-12.8

99.5

31

-0.6

185.7

65

18.3

13.5

-35

-37.2

62.3

10

-12.2

101.6

32

0.0

201.5

70

21.1

17.2

-30

-34.4

63.9

11

-11.7

103.6

33

0.6

218.2

75

23.9

21.4

-25

-31.7

65.4

12

-11.1

105.7

34

1.1

235.9

80

26.7

25.9

-20

-28.9

67.0

13

-10.6

107.9

35

1.7

254.6

85

29.4

27.8

-18

-27.8

68.6

14

-10.0

110.0

36

2.2

274.3

90

32.2

29.7

-16

-26.7

70.2

15

-9.4

112.2

37

2.8

295.0

95

35.0

31.8

-14

-25.6

71.9

16

-8.9

114.4

38

3.3

316.9

100

37.8

33.9

-12

-24.4

73.5

17

-8.3

116.7

39

3.9

339.9

105

40.6

36.1

-10

-23.3

75.2

18

-7.8

118.9

40

4.4

364.1

110

43.3

38.4

-8

-22.2

77.0

19

-7.2

121.2

41

5.0

389.6

115

46.1

40.7

-6

-21.1

78.7

20

-6.7

123.6

42

5.6

416.4

120

48.9

43.1

-4

-20.0

80.5

21

-6.1

125.9

43

6.1

444.5

125

51.7

45.6

-2

-18.9

82.3

22

-5.6

128.3

44

6.7

474.0

130

54.4

48.2

0

-17.8

84.1

23

-5.0

130.7

45

7.2

505.0

135

57.2

49.5

1

-17.2

85.9

24

-4.4

133.2

46

7.8

537.6

140

60.0

50.9

2

-16.7

87.8

25

-3.9

135.6

47

8.3

571.7

145

62.8

52.2

3

-16.1

89.7

26

-3.3

138.2

48

8.9

607.6

150

65.6

53.6

4

-15.6

91.6

27

-2.8

140.7

49

9.4

645.2

155

68.3

55.0

5

-15.0

DANGER

The refrigeration circuits are high pressure systems.

Hazards exist that could result in personal injury or death. It

is therefore required that the removal and installation of this

scroll compressor be performed by a technician qualified in

R-410A refrigerant. See Hazard Levels, page 2.

DANGER

Never use oxygen to pressurize a refrigeration system. Oxygen

can explode on contact with oil and could result in personal injury

or death. When using high pressure gas such as nitrogen for

this purpose, ALWAYS USE A PRESSURE REGULATOR that can

control the pressure down to 1 or 2 psig. Failure to use a regulator

will result in extremely high pressure which could exceed the

burst pressure of the compressor or other system components

and result in personal injury or death. See Hazard Levels, page 2.

3.6 Compressor

Maintenance

and

Replacement

3.5 Check Refrigerant Pressure and Temperatures (subcooling and superheat)

(cont'd)

3.0 Maintenance/Service Procedures (cont'd)

Temperature/Pressure Conversion Chart