beautypg.com

Reznor MAPS III, Cabinet D RECB Users Manual User Manual

Page 27

background image

Form O-MAPSIII Cabinet D, P/N 222918R9, Page 27

1) Call for Heat - The IQ controller calls for heat (there is a closure between "R" and

"W" and at least 2 VDC to the analog input). The ignition system circuit board will check

the modulating valve position and move to lightoff position. It checks to see that the limit

switch is closed and the pressure switch is open. If the pressure switch is closed, the

circuit board will wait indefinitely for the switch to open. If the switch is open, the circuit

board proceeds to prepurge.
2) Prepurge - After the actuator moves to its lightoff position, the circuit board ener-

gizes the venter motor and waits for the pressure switch to close. If the pressure switch

does not close at the beginning of a heat cycle, the venter motor will run for two min-

utes, then cycle off for 30 seconds, then on for two minutes, and so forth indefinitely.

When the pressure switch is proven closed, the venter motor ramps up to the appropri-

ate lightoff speed and the circuit board begins the prepurge time. If flame is present any

time while in prepurge, the prepurge time is restarted. If flame is present long enough to

cause lockout, refer to the Troubleshooting Guide in Paragraph 6.2.2. The ignition sys-

tem circuit board runs the venter motor for a 30-second prepurge time, then proceeds

to the ignition trial period.
3) Ignition Trial Period - The ignition system circuit board energizes the spark and

main gas valve. The venter remains energized. If flame is sensed during the first 6

seconds, the spark is de-energized. If flame has not been sensed during the first 6

seconds, the control de-energizes the spark output and keeps the gas valve energized

for an additional one second flame proving period. If flame is not present after the flame

proving period, the control de-energizes the gas valve and proceeds with three ignition

re-tries as specified in “Abnormal Heat Cycle, Ignition Retry”. If flame is present, the

circuit board proceeds to steady heat. After three re-tries, the board will lockout for one

hour. It will require a cycling of power to reset before the one-hour limit.
4) Modulating Heat - As long as the call for heat exists, the circuit board not only

modulates the gas to precisely meet varying load conditions, but also modulates the

combustion air to maintain stable performance and optimize thermal efficiency across

the entire modulating range. Circuit board inputs are continuously monitored to ensure

limit switch is closed and flame is established. When the call for heat is removed, the

ignition system circuit board de-energizes the gas valve and begins postpurge timing.
5) Post Purge - The venter motor output remains on for a 45 second postpurge period

after the system controller is satisfied.

Modulating Gas

Control Sequence of

Operation (single heat

section sizes and the

heat section furthest

from the blower on

dual heat section sizes

- natural gas only)

Ignition Controller on Non-Modulating Gas-Fired Furnace on MAPS D Sizes 1000, 1200,

1400, or 1600 with Two Furnaces

Control Status - Green LED Codes

Steady ON ...... Normal Operation, No call for heat

Fast Flash ....... Normal Operation, Call for heat

1 Flash ............ System Lockout, Failed to detect or sustain flame

2 Flashes ........ Pressure Switch Did Not Close within 30 Seconds

of Venter Motor

3 Flashes ........ High Limit or Flame Rollout Switch Open

4 Flashes ........ Pressure Switch is Closed Before Venter Motor is

Energized

Steady OFF .... Blown fuse, No Power, or Defective Board
Flame Status - Yellow LED Codes

Steady ON ...... Flame is sensed

Slow Flash ...... Weak flame (current below 1.0 microamps ± 50%)

Fast Flash ....... Undesired Flame (valve open and no call for heat)

FIGURE 14 - DSI Integrated Control

Module (Ignition Board) used on

Non-Modulating Heat Section

DSI Integrated Control Module (ignition system circuit board) - See FIGURE 14.

The module is located in the control compartment and monitors the operation of the

gas heater including ignition. The green and yellow LED indicator lights flash to indi-

cate normal and abnormal conditions. If the heater fails to operate properly, check

these signals to determine the cause and/or to eliminate certain causes. The only

replaceable component is the 3 amp Type ATC or ATO fuse. If the fuse is blown, the

problem is most likely an external overload. Correct the problem and replace the fuse

(field supplied or P/N 201685).