beautypg.com

Reznor MAPS III, Cabinet D RECB Users Manual User Manual

Page 31

background image

Form O-MAPSIII Cabinet D, P/N 222918R9, Page 31

Ball Valve with actuator removed (for

illustration only); do not remove actuator.

Ball Valve Actuator

Modulates the Gas Flow

Actuator

Setscrew

(shown on the

right or closed

position)

Ball Valve Shaft

FIGURE 18 - Ball Valve with Actuator in Modulating Gas Control Manifold

FIGURE 19 -

Gas Manifold

Transducer

Location: See FIGURE 15.

Function: The transducer reads the manifold pressure and sets the venter motor

speed to precisely match the designed combustion settings.
Service: If the transducer needs to be replaced, use only a factory-authorized replace-

ment part designed for the purpose.

Modulating System

Gas Valve (Ball

Valve & Actuator)

Adjustment

Inspect the position of the ball valve shaft.

In the fully open position, the dash marks on the top of the shaft should be aligned

with the gas piping.

In the fully closed position, the dash marks on the top of the shaft should be

aligned at a 90° angle across the gas piping.

If the ball valve shaft is not properly aligned or if the manifold pressure does not match

the settings in the chart below, the ball valve will need to be adjusted.

Manifold Pressures

for MAPSIII Cabinet

D Gas Modulation

System

Manifold Pressure (" w.c.) Measured

at the Pressure Tap by the Gas Transducer

Cabinet and Heat

Section Size

Gas Type*

High Setting

100% on ModHeat

Low Setting

0% on ModHeat

D-Cab - All Sizes

Natural

3.4

0.20

Cabinet and Heat Section Size Gas Type High Setting 100% t Low Setting 50%

D-Cab 1000

Propane

10.0

5.0

D-Cab 1200

Propane

10.0

5.0

D-Cab 1400

Propane

10.0

5.0

D-Cab 1600

Propane

10.0

5.0

*NOTE: Propane is

available on limited sizes

with 2-stage gas control

only. Manifold pressures

(valve output) for those

sizes are listed below

.

To check and/or adjust gas modulation:

Checking modulation requires a manometer capable

of reading to 0.10" w.c. Connect the manometer as

instructed in Step 1.f) below.

To check and adjust the modulation system, the IQ

controller must be in

Test Mode. On the control display

in the electrical compartment, follow the steps below to

enter

Test Mode.

a) Scroll down to Menus and press Enter.

b) Enter password (0000) using the INC button and

the right arrow button and press

Enter.

c) Scroll down to the Service Menu and press Enter.

d) Scroll down to Test Mode and press Enter.

e) Scroll down to Manual Test; press Enter; press the

INC button to change the command from OFF to

ON; and press Enter.

f) After the system has completed the shutdown

sequence, connect the gas manometer to the

manifold pressure tap next to the transducer (See

FIGURES 15 and 19).

g) On the display, scroll down to Heat Stg 1 and press

Enter.

h) Scroll down to ModHeat which has a default setting

of 100%.

2. With the

ModHeat set at 100%, measure the manifold

pressure. If the manifold pressure matches the High

Setting value in the chart above, continue to Step No.

3.

Instructions