Chapter 3: Programming

Concord 4 Installation Manual

63

Flow battery report

Shortcut: 06013

Default: Weekly

This setting determines whether the panel sends daily (1) or weekly
(2) low battery reports to the central monitoring station when a
wireless device is reporting a low battery condition to the panel.

RF low battery report

Shortcut: 06013

Default: Weekly

This setting determines whether the panel sends daily (1) or weekly
(2) low battery reports to the central monitoring station when a
wireless device is reporting a low battery condition to the panel.

RF supervisory report

Shortcut: 06014

Default: Weekly

This setting determines whether the panel sends daily (1) or weekly
(2) reports to the central monitoring station when the panel detects a
supervisory condition in a wireless device.

Swinger limit

Shortcut: 06015

Default: 1

This setting determines the maximum number of times (1 or 2) a
sensor or zone can go into alarm (during a single arming period)
before the panel automatically bypasses that sensor or zone. This
feature only applies to sensors or zones in groups 00

–20, 29, 34, 35,

or 38.

When set to 1, the panel automatically bypasses a sensor or zone
after it causes an alarm. When set to 2, the panel waits until a sensor
or zone has caused a second alarm (during the same arming period)
before bypassing it. At any setting, the automatic bypass is logged
into the event buffer.

A bypassed sensor or zone will be cleared (automatically
unbypassed) if the system receives no further activations from that
sensor or zone over the next 48 to 50 hours.

Changing the arming level also clears all automatically bypassed
sensors and zones and resets the swinger limit count on all sensors
and zones.

Auxiliary power
failure

Shortcut: 06015

Default: On

When this setting is on, the panel sends a report to the central
monitoring station if the 12 VDC power outputs on the panel and/or
SuperBus 2000 2-amp power supply fail.

If this feature is on and the AC failure and low CPU battery features
are both on, the panel sends AC failure and low backup battery
reports for the SuperBus 2000 2-amp power supply.

Ground fault

Shortcut: 06017

Default: On

When this setting is on, the panel will annunciate and send a report to
the central monitoring station if it detects current flow between the
panel’s circuitry and the chassis. This indicates that a short to earth
ground exists somewhere in the system.

This feature must be on if hardwired smoke sensors are used in this
system.