Chapter 4: Testing and troubleshooting

Concord 4 Installation Manual

111

• Touchpad is not connected to panel bus terminals or is wired incorrectly.

Check and correct wiring.

• Check that touchpad is learned into panel memory.

Display is blank.

• Check that panel is powered up.

• Check for touchpad power and/or incorrect bus wiring, opens, or shorts.

• Check the touchpad brightness setting. (See the user-programming Options

menu on page 108.)

Touchpad buttons don’t beep when pressed.

• Check for touchpad power and/or incorrect bus wiring, opens, or shorts.

• Check that key beeps option is set to on. (See the Accessory modules - bus

device settings on page 93.)

Speaker issues

Speakers don’t sound alarms.

• Speaker output has shut down because panel detected terminal 7 or 8 is

shorted to ground. Disconnect panel AC and battery backup power. Locate
short and correct. Apply panel AC and backup battery power and retest.

• Alarm is in partition 2 to 6 and speaker is connected to panel terminals 7 and

8, which activate only for partition 1 alarms.

Siren issues

Piezo sirens connected to SnapCard, or onboard (panel) outputs 1 and/or 2
don’t produce any alarm sounds.

• Check for incorrect wiring between siren and panel, and correct where

necessary.

• Output has not been configured (set up) to activate sirens. Enter program

mode and configure output. (See Accessory modules - bus device settings on
page 93.)

• Check for correct output partition assignment.

• Check that your wires are connected to the appropriate terminals:

Output 1 (exterior) uses terminals 9 (positive) and 13 (ground).
Output 2 (interior, follows status beeps) uses terminals 11 (positive) and 10
(ground).