Chapter 2: Installation

6

Concord 4 Installation Manual

Installation overview

Before starting the installation, plan your system layout and programming using
the worksheets provided in Appendix A

“System planning sheets” on page 117.

Note:

Class 2, Class 3, and power-limited fire alarm circuits must be installed

using FPL, FPLR, FPLP, or substitute cable permitted by the National Electrical
Code ANSI/NFPA 70 or Class 2, Class 3, and power-limited fire alarm circuit
conductors must be installed as Class 1 or higher circuits.

Note:

Class 2, Class 3, and power-limited burglar alarm circuits must be installed

using CL2, CL2R, CL2P, or substituting cable permitted by ANSI/NFPA 70. Wire
that extends beyond the cable jacket must be separated from all other
conductors by a minimum of 0.25 in. or by a nonconductive barrier.

Use the following installation guidelines:

• Centrally locate the panel with relation to detection devices whenever

possible, to help reduce wire run lengths and labor.

• Locate the panel where the temperature will not exceed 120°F (49°C) or fall

below 32°F (0°C).

• Avoid running wires parallel with electrical wiring or fixtures such as

fluorescent lighting, to prevent wire runs from picking up electrical noise.

• Mount the panel at a comfortable working height (about 45 to 55 in. from the

floor to the bottom of the panel, as shown in Figure 1 on page 7).

• Leave space to the left and right of the panel for wiring, phone jack, and

mounting optional modules. Allow at least 9 in. (23 cm) above the panel
cabinet for antennas. Allow at least 24 in. (62 cm) in front of the panel to open
the panel door.